RUGGEDCOM RX1100P
Installation Guide
Chapter 2
Installing the Device
Grounding the Device
15
1
3
2
Figure 12: Failsafe Alarm Relay Wiring
1.
Normally Open
2.
Common
3.
Normally Closed
Section 2.4
Grounding the Device
The RX1100P chassis ground terminal uses a #6-32 screw. It is recommended to terminate the ground
connection with a #6 ring lug and torque it to 1.7 N·m (15 lbf·in).
2
1
3
Figure 13: Chassis Ground Connection
1.
Stainless Steel Stud
2.
#6-32 Screw
3.
#6 Ring Lug
Section 2.5
Cabling Recommendations
Siemens does not recommend the use of copper cabling of any length for critical, real-time substation automation
applications. All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry
to protect against damage from electrical transients and conform with IEC 61850-3 and IEEE 1613 Class 1
standards. This means that during a transient electrical event, communications errors or interruptions may occur,
but recovery is automatic.