Chapter 2
Installing the Device
RUGGEDCOM RX1100P
Installation Guide
8
Connecting Power
2
1
1
Figure 4: Panel Mounting
1.
Screw
2.
Panel/DIN Rail Adaptor
2. Install the supplied screws to secure the adapters to the panel.
Section 2.2
Connecting Power
The RX1100P supports single or dual redundant AC and/or DC power supplies. The use of two power modules is
recommended to provide redundancy and load balancing.
The RX1100P supports a single AC or DC power supply, and a separate 48 VDC power supply for PoE ports.
The RX1100P can be equipped with either a screw-type or pluggable terminal block, which provides power to
the AC/DC power supply and PoE ports. The screw-type terminal block is installed using Phillips screws and
compression plates, allowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for
secure, reliable connections under severe shock or vibration.
NOTE
• For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 88-300 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• Use only #16 gage copper wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
• It is recommended to provide a separate circuit breaker for each power supply module.