Certification
6.2 EMC and Environmental Type Tests
EMC Type Tests per IEC 61850-3
Test
Description
Test Levels
Severity Levels
Enclosure Contact
±8 kV
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
IEC 61000-4-4
Burst (Fast
Transient)
Earth Ground
Ports
±4 kV
4
Signal Ports
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
DC Power Ports
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced
(Conducted) RFI
Earth Ground
Ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure Ports
100 A/m
Continuous
1000 A/m for 1 s
5
IEC 61000-4-11
Voltage Dips
and Interrupts
AC Power Ports
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12
Damped
Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @1 MHz
3
Signal Ports
IEC 61000-4-16
Mains Frequency
Voltage
AC and DC
Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
15%
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
2 kV (Fail-Safe
Relay Output)
IEC 60255-5
Dielectric Strength
DC Power Ports
2 kV
42
RUGGEDCOM RSG2300F
Installation Manual, 04/2021, C79000-G8976-1347-09