Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
AC Power Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Only applicable to functional earth connections separated from the safety earth connection.
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG2300F meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Description
Test Levels
Enclosure Contact
±2 kV
±8 kV
ESD
Enclosure Air
±15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
4 kV @ 2.5 kHz
DC Power Ports
4 kV
AC Power Ports
4 kV
Fast Transient
Earth Ground Ports
4 kV
Signal Ports
2.5 kV Common Mode @ 1 MHz
DC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Fail-Safe Relay Output)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
2 kV
Dielectric
Strength
AC Power Ports
2 kV
Damped
Oscillatory
Magnetic Field
Enclosure Ports
100 A/m
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
RUGGEDCOM RSG2300F
Installation Manual, 04/2021, C79000-G8976-1347-09
43