Central control unit RMB795B
CE1P3122en
Building Technologies
Distribution zones
18.01.2012
11.1.2 Indirect application
RMH760
RMH760
RMB795
Konnex TP1
RXB...
RXB...
RXB...
T
T
T
T
1
2
3
31
21
Z
11e
n
Heat requistion
Heat demand
Heat distr zone
consumer side: 1
Heat source
Controller 1
Controller 2
Controller 3
Controller 4
Controller 5
Controller 6
Controller 1
Controller 2
Controller 3
Controller 4
Controller 5
Controller 6
Heat demand
Heat demand
Heat demand
Heat demand
Heat demand
Heat requistion
Heat requistion
Heat distr zone
source side: 1
Heat distr zone
source side: 2
Heat distr zone
source side: 3
Heat distr zone
source side: 3
Heat distr zone
source side: 3
Heat distr zone
consumer side: 2
Heat distr zone
consumer side: 3
Heating circuit
fan coil
Fan coil
room A
Fan coil
room B
Fan coil
room C
DHW heating
Setting values
With this type of application, the individual RXB/RXL room controllers signal their
heat demand indirectly to the heat source via the RMB795B central control unit.
This type of application is used for 2 reasons:
a) From the RMB central control unit, the heat demand signal is passed on to an
external primary controller or heat source via a modulating output or relay
output
b) To reduce the KNX network load, the request signals are collected on the RMB
central control unit and passed on as heat demand signals to the heat source
via a line coupler.
(1), (2) and (3) designate the numbers of the distribution zone.
This type of application can analogously be applied to refrigeration distribution
zones.