Function block: "Room group"
18.01.2012
8.8.1
Priorities
Priority sequence for individual room controller room operating mode/individual
room control:
1. Smoke
extraction
2. Fire alarm off
3. Room operating mode/control functions (combined)
4. Optimum start control
5. Night
cooling
8.9
Night cooling
The "Night cooling" function is used in the summer during non-occupancy times to
cool down the rooms with cool outside air.
Cooling energy can thus be saved during occupancy times.
8.9.1
Activate function
For the "Night cooling" function to be activated, the following conditions must be
satisfied:
•
At least 1 reference room temperature must be available
•
Outside temperature must be available.
For acquisition of the reference room temperature, following applies:
In the Communication menu, you can define 1 to 3 individual rooms from the
corresponding room group as a reference room by assigning the geographic zone
(room), see Sec. 13.2.2 "Room group 1...10".
•
Of the maximum of 3 reference rooms, it is always the highest room temperature
that is selected
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1....10 > Night cooling >
Operating line
Range
Factory setting
Outside temperature
limit
0...50 °C
12 °C
Room-outside temp
delta
0.0...20.0 K
5 K
Operating time min
0...720 min
30 min
Precooling time max
0...2880 min
0 min
Night cooling function is disabled by setting the the parameter "Precooling time
max" to 0 minutes (default value).
8.9.2
Operating principle
When individual room controllers are used on applications that support the "Night
cooling" function, the room controllers can be released via the RMB795B central
control unit.
For detailed information about RXB/RXL room controllers that support the "Night
cooling" function, refer to the relevant RXB/RXL documentation.
Purpose
Conditions
Reference rooms
Setting values
Deactivate night cooling
Use and release