![Siemens RMB795B Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/siemens/rmb795b/rmb795b_basic-documentation_377324063.webp)
63 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
8.3.5
7-day time switch
Every function block "Room group" has its own 7-day time switch. This time switch
is firmly coupled to the relevant room group.
The 7-day time switch controls the change of the operating modes and the
associated setpoints in accordance with the 7-day program entered.
Different times from one week to another are not possible.
Operation of the 7-day time switch is described in the operating instructions B3121.
A specific 24-hour profile can be selected for the following weekdays.
Main menu > Room group 1…10 > Time switch
Operating line
Range
Factory setting
Monday through
Sunday
Comfort, Precomfort,
Economy.
06:00 Comf.
22:00 Eco
Special day
Comfort, Precomfort,
Economy.
06:00 Comf.
22:00 Eco
Activation of special day is described in Sec. 13 "Communication".
Every day can be assigned a maximum of 6 entries in the 24-hour program.
Entries required for an entry:
•
Time of day from which the desired operating mode shall apply
•
Desired operating mode.
When all entries for one day have been made, that day can be copied to the other
days. In that case, the respective time switch must be selected (e.g. Room group 1
> Time switch > Monday).
When turning the OK knob in clockwise direction, the selection "Copy to" will
appear at the end of the time switch entries. You can copy to Monday-Friday,
Monday-Sunday or each day of the week.
When all entries have been made in a 7-day program, that program can be copied
to other room groups. In that case, the respective time switch must be selected
(e.g. Room group 1 > Time switch).
When turning the OK knob in clockwise direction, the selection "Copy to" will
appear at the end of the list of weekdays. Here, you are given the choice of
copying to all room groups or to each individual one.
The copy process will only take place if the target room group in the function block
is enabled.
For each "Time switch zone (Apartm)", only one time switch master may be set. If
several devices are parameterized as masters, a fault status message occurs.
Assignment and
function
Setting values
Activation of the
special day
Copy 24-hour profiles
Copying 7-day
programs
Note
Troubleshooting