![Siemens RMB795B Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/siemens/rmb795b/rmb795b_basic-documentation_377324039.webp)
39 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
General settings
18.01.2012
6.1.2
Communication
Depending on the master clock , different sources for the time of day can be used.
This can be selected on the RMB795B central control unit. Time of day and date
can be exchanged via bus.
The following setting available for clock time operation:
•
Autonomous (does not transmit and does not receive)
•
Clock time
from
the bus: Clock time slave (receives the synchronization signal
from the bus)
•
Clock time
to
the bus: Clock time master (sends the synchronization signal to
the bus)
Commissioning > Communication > Basic settings >
Operating line
Range
Factory setting
Clock time operation
Autonomous, slave, master. Autonomously
If the central control unit is set as a time-of-day slave, it can also be selected
whether it shall be possible to adjust the master clock’s time of day from this
central control unit.
For remote adjustment of the clock slave, the following setting choices exist:
•
No (clock time slave with no adjustment facility for the system time).
•
Yes (clock time slave with adjustment facility for the system time).
Commissioning > Communication > Basic settings >
Operating line
Range
Factory setting
Remote setting clock
slave
Yes, no
Yes
The above settings have the following impact:
Entry
Effect
Diagram
Autonom
ously
The clock time on the central control unit can
be adjusted.
The central control unit’s clock time will not
be adapted to the system time.
Con. time
Sys. Time
Adjustment
Slave
,
remote
setting
clock
slave
No
The clock time on the central control unit
cannot be adjusted.
The central control unit’s clock time is
continuously and automatically adapted to
the system time.
Con. Time
Sys. Time
Adjustment
Slave
,
remote
setting
clock
slave
Yes
The clock time on the central control unit can
be adjusted and, at the same time, adjusts
the system time.
The central control unit’s clock time is
continuously and automatically adapted to
the system time.
Con. Time
Sys. Time
Adjustment
Master
The clock time on the central control unit can
be adjusted and, at the same time, adjusts
the system time.
The time of day for the central control unit is
used for the system.
Con. Time
Sys. Time
Adjustment
Only 1 clock time master per system may be used. If several devices are
parameterized as master, a fault status message (to the master) will be delivered.
Clock time operation
Setting values clock time
operation
Setting values remote
setting clock slave
Impact of setting
values
Note