![Siemens RMB795B Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/siemens/rmb795b/rmb795b_basic-documentation_377324036.webp)
36 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Commissioning
18.01.2012
5.8
Exit password level
On completion of commissioning, set the user level, i.e. access level for the plant
operator. To do this, exit the main menu and proceed as follows:
Step
Action
Result
1
Press simultaneously the
OK
knob and the
ESC
button
The
Access levels
menu is
displayed.
2
Select the user level by turning the
OK
knob
and confirm by pressing the knob.
The selected user level is set
and the previous menu
reappears.
5.9
View device information
Important information about the RMB795B central control unit, the connected
extension modules, the configuration and the communication settings can be
viewed on the
Device information
menu.
Main menu > Device information > Controller
Operating line
Comments
Basic type
Display of application (application "B") loaded during
commissioning.
Adapt basic type
Display of intervention in the programmed application
(yes, no)
File name
Name of an application that was downloaded by the
ACS
Device type
Display of the device used (e.g. RMB795B-1).
software version
Display the software version.
Hardware version
Displays hardware version.
Main menu > Device information > Position 1…3
Operating line
Comments
Extension module.
Display of the module’s type reference.
software version
Display of the module’s software version
Hardware version
Displays hardware version.
Main menu > Device information > Extra configuration
All settings for extra configurations can be read under this menu. This offers a
quick overview of the connections used in the configuration.
Main menu > Device information > Communication
All communication settings can be viewed here.
5.10 Mark an intervention
When the internal standard application (that is, basic type "B" ) was adapted, or the
Extra configuration
menu was subsequently accessed, an asterisk will be set on
Set user level
Purpose
Display values
ID