Central control unit RMB795B
CE1P3122en
Building Technologies
Operation
18.01.2012
2 Operation
Synco™ 700 devices may only be operated by staffs who has been instructed
by Siemens Building Technologies or their delegates and whose attention
has been drawn to potential risks.
2.1
Operation without operator unit
Without the operator unit, the following operating elements on the central control
unit RMB795B and extension module can be used:
31
4
0Z02
1
2
3 4
31
40
Z
03
5
Central control unit
Extension module
The operating elements shown above have the following functions:
Ref.
Operating element
Function
1 LED
Run
Indication of the unit’s operating state:
LED lit:
Power on, correct use and no fault in
the peripheral devices
LED off:
No power or incorrect use / faulty
peripheral devices
2
Fault button
with LED (red)
Indication and acknowledgement of a fault status
message:
LED flashes:
Fault status message ready for
acknowledgement
LED lit:
Fault status message still present but
not yet reset
LED off:
No fault status message present
Press button
Acknowledge fault or reset.
3
Prog
button
Learning button for switching between normal mode
and addressing to adopt the physical device address
(tool required)
4 LED
Prog
LED to indicate "Normal mode" (LED off) or
"Addressing mode" (LED on); it extinguishes after
adoption of the physical address
5 LED
Run
Supervision of power supply and addressing:
LED lit:
Power on, module addressing lit
LED flashes:
Power on, but module not yet
addressed by the RMB795B central
control unit
LED off:
No
power
Operating elements
Functions