![Siemens RMB795B Скачать руководство пользователя страница 119](http://html.mh-extra.com/html/siemens/rmb795b/rmb795b_basic-documentation_377324119.webp)
119 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
RXB/RXL operation
18.01.2012
14 RXB/RXL
operation
14.1 Operation of individual RXB/RXL room
controllers
The description of the data points applies to both RXB and RXL.
Using menu item
Operation RXB/RXL
, a number of RXB/RXL data points can be
read and written. These are specially selected values, such as:
•
Room number
•
Actual values and setpoints
•
Operating mode
•
Current heat and refrigeration requests, etc.
The data points displayed at a time depend on the type of RXB/RXL room
controller used and its application.
For the relevant RXB/RXL room controller to be addressed, its geographical zone
(apartment and room) must be entered. The relevant information can then be read
under the
RXB/RXL device data
menu.
The first data points displayed are the room number and the description, which give
the user an unambiguous reference.
Updating of values can take a few seconds. During this period of time, the values
are displayed as " --- ".
Data points not available in the room controller are also displayed as " --- ".
If the RMB/RXL is operated in an interconnected device system with a line couple
and is in another area, the corresponding line couples must be set to "Route all" /
"route" (by the corresponding GeoZones).
Main menu >RXB / RXL operation >
Operating line
Range
Factory setting
Geographical zone
(apartment)
---,1...126 ---
Geographical zone (room) ---,1...63
---
Main menu > RXB / RXL operation > RXB / RXL device data
Operating line
Description
R /
W
Room number
Text string stored in RXB/RXL.
R
Device name
Text string stored in RXB/RXL.
R
Active HVAC operating mode Active HVAC room operating mode
(Comfort / Pre-Comfort / Economy /
Protection).
R
Actual value room temp
Actual value room temp
R
Present setpoint
R
Economy cooling setpoint
W
Precomfort cooling setpoint
W
Comfort cooling setpoint
W
Comfort heating setpoint
W
Precomfort heating setpoint
W
Economy heating setpoint
W
What can be operated?
Menu and displays
Setting values
Display values