Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Distribution zones
18.01.2012
11.5 "Refrigeration demand" function block
11.5.1 Purpose
The function block generates a "Refrigeration demand" signal that can be used by
other devices. The refrigeration demand is provided in the form of the following
signals:
•
Digital signal at output Q ("Refrigeration demand relay")
•
Analog signal at output Y ("Refrigeration demand modulating")
•
Bus signal ("Communication")
Q
Y
Q
Y
Relay
Refrigeration demand
The 3 variants are described below.
11.5.2 Refrigeration demand relay
The refrigeration demand relay must be configured to a relay output N.Qx of the
RMB795B central control unit. Release for an external refrigeration source, e.g.,
can be connected to this output.
The refrigeration demand relay responds as soon as the bus requests refrigeration.
Meaning:
•
Contact open
=
No refrigeration demand.
•
Contact closed =
Refrigeration demand
Main menu > Commissioning > Extra configuration > Demand for refrigeration
Operating line
Adjustable values / remarks
Refrigeration demand
relay
---, N.Q1, N.Q3, ... /
activation of output
11.5.3 Refrig demand modulating
In addition to the refrigeration demand relay, the refrigeration demand can be
provided at a modulating output N.Yx for other devices.
Main menu > Commissioning > Extra configuration > Demand for refrigeration
Operating line
Adjustable values / remarks
Refrig demand
modulating
---, N.Y1, N.Y2
activation of output
Main menu > Settings > Refrigeration demand >
Operating line
Range
Factory setting
Setpoint at 0 V
–50…+50 °C
12 °C
Setpoint at 10 V
50…500 °C
6 °C
Limit value.
–50…+250 °C
12 °C
"Refrigeration demand"
signal generation
Purpose and function
Configuration
Purpose
Configuration
Setting values