24 Overexcitation Protection
Common Settings
Reference
Parameter
Value
Input selection
Definite Time Element (24DT)
Reference
Parameter
Value
V/f
set
Setting
0.10 to 2 ⋅ V
rated
/f
rated
V/f
Applied overexcitation (for operate time)
0.9 to 1.1 V/f
set
0.9 to 2 V/f
set
t
delay
Delay setting
0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute
Value
V/f
op
Operate level
100 % ⋅ V/f
set
: ± 2 % or ± 0.02
Reset level
≥ 97 % of V/f
op
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
1.1 ⋅ V/f
set
: 400 ms ± 200 ms
2 ⋅ V/f
set
: 320 ms ± 200 ms
t
op
Operate time following delay
t
basic
+ t
delay
± 1 % or ± 200 ms
Repeatability
± 1 %
Disengaging time
< 250 ms
Inverse Time Element (24IT)
Reference
Parameter
Value
t
reset
Reset setting
0 to 1000 s, Δ 1 s
10.3
10.3.1
10.3.2
10.3.3
Technical Data
10.3 24 Overexcitation Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
459
C53000-G7040-C015-1, Edition 11.2019
Содержание Reyrolle 7SR5
Страница 8: ...8 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 24: ...24 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 132: ...132 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 142: ...142 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...
Страница 338: ...338 Reyrolle 7SR5 Transformer Protection Device Device Manual C53000 G7040 C015 1 Edition 11 2019 ...