Logic of the Function
[lo_7SR5_27Vxlogicdiagram, 1, en_US]
Figure 5-5
Logic Diagram: 27Vx Undervoltage Protection – Vx
Application and Setting Notes
Parameter:
27Vx Common > UV Guard Setting
•
Default setting:
5 V
When the measured voltage is below this setting operation of the 27Vx function elements can be
blocked.
Parameter:
Element
•
Default setting:
Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. These settings can be used to select the number of elements required.
5.4.3
5.4.4
Protection and Automation Functions
5.4 27Vx Undervoltage Protection – Vx
166
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019