Functions
Control sequences
4
66 | 150
A6V11545892_en--_a
4.7.7 4-pipe fan coil unit
In 4-pipe applications, the thermostat controls 2 valves in heating and cooling
mode, heating/cooling mode by manual selection, or heating and cooling mode
with changeover. Heating and cooling mode (P001 = 4) is factory-set.
The heating or cooling output can be released via operating mode button if P001 is
set to Manual (P001 = 3).
The diagrams below show the control sequence for On/Off control.
Heating and cooling mode (P001 = 4)
T[°C] Room temperature
w Room temperature setpoint
YH Control command "Valve"
(heating)
YC Control command "Valve"
(cooling)
SDH Switching differential "Heating"
(P051)
SDC Switching differential "Cooling"
(P053)
X
dz
Dead zone (P055)
Heating mode with manual selection
(P001 = 3) or
energy saving (P010 = 2 & P014) in
heating sequence
Cooling mode with manual selection
(P001 = 3) or
energy saving (P010 = 2 & P015) in
cooling sequence
The diagrams below show the control sequence of modulating PI control.
Heating and cooling mode (P001 = 4)
T[°C] Room temperature
w Room temperature setpoint
YH Control command "Valve"
(heating)
YC Control command "Valve"
(cooling)
XpH Proportional band "Heating"
(P050)
XpC Proportional band "Cooling"
(P052)
X
dz
Dead zone (P055)
Heating and cooling
4-pipe application with
manual changeover
On/Off control
Modulating control:
3-position, PWM, or
DC 0...10 V