6.3 Application examples
The examples are described for RDG260KN, but they also apply to RDG200KN.
Control output (P201, P204) and terminals for the valves (Y1, Y2) need to be
adapted accordingly.
6.3.1 Humidity control
In the following examples, P461 is configured based on the connected type of
equipment. See details in Humidity [
52].
2-pipe fan coil application for dehumidification, with temperature setpoint shifting
and dehumidifier contact, DC 0...10 V fan and DC valve:
Commissioning
Outputs used
●
Fan P351 = 3
(or DIP6 = OFF)
●
Control strategy P450 = 1
●
Setpoint high P024 = 50 %
(factory setting)
●
Temp. shift P461 = 3 K
(factory setting)
●
Valve P201 = 5
●
Relay function P402 = 7
(dehumidifier)
●
M1 DC 0...10 V fan
●
V1 DC valve
●
L3
*)
Dehumidifier
*)
Release contact
140] for min. and
max. ratings
RDG260KN
Note:
Example 1: Dehumidifier,
DC 0...10 V fan and valve