background image

 

 
 
 
 
 

RAB20 Series 

Technical Instructions

Document No. 155-526P25

ET RAB-2

March 2, 2007

Two-pipe Fan Coil Room 
Thermostat with Automatic 
Changeover 

 
 

 

 

RAB20.1 

Description 

Two-wire, gas diaphragm-based fan coil room thermostat for heating or cooling 
systems with two-pipe fan coil applications. 

Features 

 

 

 

 

 

 

 

 

Automatic 

changeover 

Manual, three-speed fan switch 

Fan release function 

Dual setpoint temperature scale 

Two-point control algorithm (On/Off) 

24 to120 Vac, 277 Vac operating voltage 

Two mounting styles: electrical wall box or drywall 

Wall plate adapter (ARG70) included with electrical wall box mount styles 

Application 

The RAB20… is used in heating or cooling systems with external automatic 
changeover devices (aquastats) to maintain the selected room temperature. 

Typically used in commercial, high-rise and light industrial buildings in conjunction with: 

 

 

 Fans 

 

Zone 

valves 

Thermal 

valves 

Aqua sensors (changeover sensors, provided by others) 

Product Numbers 

See Table 1. 

Accessory 

ARG70 Wall box adapter 

Technical Design 

The RAB20… fan coil room thermostat is based on a two-wire, gas diaphragm 
technology. 

Siemens Building Technologies, Inc. 

Содержание RAB20 Series

Страница 1: ...ting voltage Two mounting styles electrical wall box or drywall Wall plate adapter ARG70 included with electrical wall box mount styles Application The RAB20 is used in heating or cooling systems with external automatic changeover devices aquastats to maintain the selected room temperature Typically used in commercial high rise and light industrial buildings in conjunction with Fans Zone valves Th...

Страница 2: ...alve Auto Fan is switched with the heating valve Ventilation When the ventilation function is selected on the RAB20 1 only the heating and cooling contacts are always open and the fan works at the selected speed Changeover Heating cooling changeover is automatic based on room temperature Changeover is achieved externally using an SPDT aqua sensor not included wired between Terminals W Y and the zo...

Страница 3: ...Off Weight 5 oz 0 14 kg Dimensions 3 80 4 45 1 68 inches 96 4 113 1 42 8 mm Color Ivory white with gray selector knobs Ambient Conditions Operation Temperature 32 F to 122 F 0 C to 50 C Relative humidity 95 Transport Storage Temperature 4 F to 122 F 20 C to 50 C Relative humidity 95 Wiring Screw terminals for wires of 2 16 AWG or 1 14 AWG minimum 20 AWG Housing Material Plastic Enclosure rating NE...

Страница 4: ...st be de energized and the operating voltage checked before opening An ARG70 wall plate adapter provided with electrical wall box mount models must be used to mount to a 2 4 inch or 4 4 inch electrical wall box An ARG70 wall plate adapter must be used to meet UL and cUL requirements The thermostat must be mounted on a flat wall All local electrical regulations must be complied with If there are th...

Страница 5: ...ion sensitive 10 Pull the wiring through the sub base 11 Position thermostat housing over the two mounting lugs located at the top of the sub base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions on the inside of thermostat cover Optional To set limit stops remove gray tabs located on the setpoint knob and position high and low stops around perimet...

Страница 6: ...hermostat base and push up to remove cover 3 Using the four screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting Steps 7 through 16 The...

Страница 7: ...rom the thermostat base and push up to remove cover 3 Using the two screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting Steps 7 throug...

Страница 8: ...S N1 G3 TH0508R3 Y I II III G2 G1 L ZV W AS Aqua sensor by others G1 Control output fan speed I Low G2 Control output fan speed II Medium G3 Control output fan speed III High L Operating voltage M1 3 speed fan N Neutral N1 Room thermostat W Valve output heating Y Valve output cooling ZV Zone valve Figure 5 Wiring W T F ON OFF SP SD TH0488R3 Heating Mode Y T F ON OFF SP SD TH0489R2 Cooling Mode SD ...

Страница 9: ...lo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions Dimensions in inches millimeters 3 80 96 4 4 45 113 1 1 68 42 8 TH0495R2 Figure 7 RAB20 Unit 1 18 30 0 66 16 9 2 56 65 1 9 7 5 0 0 5 1 1 3 2 56 65 0 51 13 1 18 30 1 38 35 0 46 11 8 1 00 25 5 3 9 99 3 38 86 Ø 0 14 3 6 Ø 0 25 6 ...

Отзывы: