background image

CC1N7221en 

27.10.2005 

Building Technologies

HVAC Products

 

 

 

7

221

 

 

 

 

 

 

QPLx2… 

QPLx5… / QPHx5… 

 

 

 

 

Pressure Switches 

QPL…

QPH…

 

 

 
 
 
The pressure switches are used for monitoring gas or air pressures. 
When the pressure falls below or exceeds the adj usted switching point, the re-
spective electrical  circuit will be  opened  or changes  over. 

 

The QPL... / QPH… and this Data Sheet are intended for use by OEMs which inte-
grate the pressure switches in their products. 
 
 
 

Use 

 

For the supervision of air or gas pressures in gas trains of gas-fired equipment (gas 
burners) 

 

The QPL... / QPH… are available as  pressure  switches  for minimum  or maximum 
pressure 

 

Suited for pressure ranges up to 500 mbar 

 

Suited for gases of gas families 1, 2 and 3 and other neutral gaseous media 

Содержание QPL Series

Страница 1: ...e electrical circuit will be opened or changes over The QPL QPH and this Data Sheet are intended for use byOEMs which inte grate the pressure switches in their products Use For the supervision of air or gas pressures in gas trains of gas fired equipment gas burners The QPL QPH are available as pressure switches for minimum ormaximum pressure Suited for pressure ranges up to 500 mbar Suited for gas...

Страница 2: ...e the pressure switch in inflammable or explosive gas atmospheres Engineering notes To set the required switching point remove the cover from the pressure switch and turn the setting knob clockwise to increase the set value or counterclockwise to decrease it see scale under Dimensions Replace the cover and secureit to prevent tampering Mounting notes Ensure that the relevant national safety regula...

Страница 3: ...rt 00739 ISO 14001 2004 Cert 38233 Disposal notes The unit contains electrical and electronic components and must not be disposed of together with domestic waste Local and currently valid legislation must be observed Mechanical design Housingmade of durable plastic with die cast aluminium base Adjustable switching point Automatic reset Manual reset at QPLx2 on request The switching point setpoint ...

Страница 4: ...A00 QPLx2 Pressure range connection O ring connection Bauform 0 7 3 mbar QPL25 003 QPL15 003 QPLx5 2 10 mbar QPL25 010 QPL15 010 QPLx5 5 50 mbar QPL25 050 QPL15 050 QPLx5 10 150 mbar QPL25 150 QPL15 150 QPLx5 100 500 mbar QPL25 500 QPL15 500 QPLx5 Pressure range connection O ring connection Bauform 5 50mbar QPH25 050 QPH15 050 QPLx5 10 150 mbar QPH25 150 QPH15 150 QPLx5 On request Connector for en...

Страница 5: ...ded Safety class QPLx2 QPLx5 QPHx5 I to VDE 0631 II to VDE 0631 Degree of protection QPLx2 QPLx5 QPHx5 IP 40 to be ensured through adequate mounting IP 54 Switching pressure deviation 15 referred to the setpoint diaphragm in vertical position Gas families I II III Typical hysteresis Type reference Switching differential QPL QPH 10 mbar 0 5 mbar QPL QPH 50 mbar 1 mbar QPL QPH 75 mbar 3 mbar QPL QPH...

Страница 6: ...n diagram Pressure switch for minimum pressure When the pressure falls below the set value NO opens and NC closes Pressure switch for maximum pressure When the pressure exceeds the set value NC opens and NO closes P COM 3 2 NO NC 1 7221d 01 1005 P COM 3 2 NO NC 1 72 21d01 1 005 QPL2 QPLx5 QPHx5 Connection examples QPLx5 QPHx5 fitted to VGD20 QPLx5 QPHx5 fitted to VGD40 Pressure switches for minimu...

Страница 7: ...e 1005 S I E M E NS 47 63 95 25 50 8 Note Dimensions for reference only Securing cover for adjusting knobs Adjusting knobs Securing screw Gas pressure test point Switch contacts Gas inlets bottom Standard base Gas inlets side and bottom optional Mounting side optional NO COM NC Gas pressure test point Gas pressure test point 722 1m05e 1 005 QPLx2 QPLx5 QPHx5 2005 Siemens Building Technologies HVAC...