Installation Instructions 

Document No. 129-484 

April 17, 2014 

 

Series 2200 Temperature and Series 
3200 Combination RH&T Room Units, 
TEC 

 

 

Item Number 129-484, Rev. JA

 

Page 1 of 3 

Product Description 

These room units allow users to view and adjust 
points in the controller using the room unit buttons 
and digital display. 

They work with various Terminal Equipment 
Controllers (TECs) and Actuator Terminal 
Controllers (ATECs) offered by Siemens Industry, 
Inc. These devices incorporate a solid state or 10K 
NTC sensing element to detect temperature (and 
humidity for QFA models). The effective sensing and 
setpoint range is 55°F to 95°F (13°C to 35°C). 

These room units can be mounted on electrical 
boxes, stud-type mounting brackets, or drywall. 
Obtain the necessary mounting hardware and follow 
the appropriate mounting procedures for the type of 
installation required. 

Product Numbers 

QAA2280.xWNC 

QFA3280.xWNC 

QAA2280.xWSC 

QFA3280.xWSC 

QAA2281.xWSC 

 

Accessories

 

AQA2200-INTL 

Room Unit Back Plate (10-pack) 

AQA2200-2X4 

Room Unit Back Plate (Single) 

563-102 GSKT Kit  Room Sensor Insulating 
 

Gasket (10-pack) 

 

(For hollow wall installations) 

TEC to Room Sensor Cable 
Yellow, 6-pin male with RJ-11 jacks on both ends 
(Choose 1, a cable may already be installed): 
588-100A  25-foot 
588-100B  50-foot 
588-100C  100-foot 

Caution Notations 

CAUTION 

 

Equipment damage or loss of 
data may occur if you do not 
follow a procedure as 
specified. 

Expected Installation Time 

20 minutes 

Required Tools 

 

Phillips sizes 1 and 2 screwdrivers 

 

Small and medium, flat-blade screwdrivers 

 

1/16-inch hex key or 544-643A Passkey 
(includes hex bit) 

 

Medium-duty electric drill 

 

3/16-inch (4.8 mm) drill bit 

 

One-inch (25 mm) hole saw 

 

Small level 

 

Tape measure 

 

Marker or pencil 

If using non-terminated or damaged cables, you also 
need: 

 

Room unit connector tool (RJ-11 crimping 
tool – SBT P/N 540-140 or third-party tool) 

 

Room unit connector kit (SBT P/N 540-141) 

Prerequisites 

 

Review these instructions before beginning. 

 

Installed: appropriate field wiring (standard 
six-conductor room unit cables, plenum or 
non-plenum as required) within the 
maximum wiring run length for the individual 
equipment controller. The maximum 
recommended length is 100 feet (30 m). 

 

All wiring must comply with National Electric 
Code (NEC) and local regulations. 

 