analog input (AI) point 

Point that receives a signal that represents a 

condition which has more than two states. For 

example, flow rate sensors (water or air), 

temperature sensors (room or duct), pressure 

sensors (static or velocity), and humidity sensors 

(room, duct or outdoor). 

analog output (AO) point 

Point that sends a signal to command equipment 

which has more than two states. For example, 

damper or valve positioners, fan inlet vane 

controllers, motor controllers, or electric heater 

controllers. 

BACnet 

Data communication protocol for Building 

Automation and Control networks, ANSI/ASHRAE 

Standard 135-1995. BACnet allows devices from 

multiple manufacturers to work together. 

BACnet Object Browser 

An application that allows you to browse Siemens 

BACnet devices and objects and third-party 

BACnet devices and objects for diagnostic 

purposes. 

BIBB 

BACnet Interoperatibility Building Blocks. 

Collections of one or more BACnet services that 

function to define the interoperational capabilities 

of a BACnet device. For more information, see the 

Building Automation and Control Networks, 

ANSI/ASHRAE Standard 135-2004. 

change-of-value (COV) 

Point trending method where each change in a 

point's value, based on a pre-defined limit, is 

recorded. 

digital input (DI) point 

Point that receives a two-state signal such as 

ON/OFF and OPEN/CLOSE. For example, low 

temperature detectors, differential pressure 

switches, flow proof switches, and door closures. 

digital output (DO) point 

Point that sends a two-state signal such as 

ON/OFF and OPEN/CLOSE. For example, two-

speed fan motor starters, two-position valves and 

dampers, pump motor starters, lighting switches, 

and chiller and boiler switches. 

HAND-OFF-AUTO (HOA) switches 

Manually operated control switches located on the 

face of HOA equipped MECs and point expansion 

modules that enable digital output points to be 

manually placed into HAND (ON), OFF, or AUTO 

control. Analog outputs can be placed into AUTO 

and nine manual control positions. 

light emitting diode 

(1) Solid state device that gives off light when 

electricity passes through it. (2) Display 

applications are classified either as low information 

content (where a limited amount of information is 

being displayed, refresh rates are slow, and the 

nature of information being displayed is 

predictable), or as high information content (where 

the opposite conditions apply). Broadly speaking 

LEDs, ELs, and VFDs are best suited to the 

former, while plasma and all types of LCDs are 

appropriate for the latter. 

Protocol Implementation Conformance 

Statement (PICS) 

Available from building automation control 

vendors, a PICS documents such things as 

supported conformance class, functional groups, 

standard application services, standard object 

types, data link layer options, character sets, and 

any special functionality built into the protocol. 

Содержание PPM-1U32.BPF

Страница 1: ...125 5065T Building Technologies 2012 08 06 MS TP Point Pickup Module Owner s Manual ...

Страница 2: ...offices and authorized distributors offer Technical Support Programs that will ensure continuous trouble free system performance For further information contact your nearest Siemens Industry Inc representative Copyright 2012 by Siemens Industry Inc FCC Regulations The manual for an intentional or unintentional radiator shall caution the user that changes or modifications not expressly approved by ...

Страница 3: ...t the dealer or an experienced radio TV technician for help Your feedback is important to us If you have comments about this manual please submit them to mailto Sbt_technical editor us sbt siemens com Credits Staefa and TALON are registered trademarks of Siemens Industry Inc Other product or company names mentioned herein may be the trademarks of their respective owners Printed in USA ...

Страница 4: ......

Страница 5: ...ported Sensor Types 9 Specifications 10 Communication RS 485 Port 11 HOA Hand Off Auto 12 DIP Switch Settings 13 Baud Rate Settings 13 Status LEDs 14 Change of Value Implementation 15 Accuracy Resolution 15 Wiring 16 I O Configuration Diagrams 17 Service Information 18 Electrostatic Discharge 18 Ordering Replacement Parts 18 Reinstalling the Mounting Tabs 18 Glossary 20 Index 21 ...

Страница 6: ...the incorporation of a cluster of remote points into the Building Automation Station over the MS TP The PPM family leverages the MS TP network to extend the reach of any BTL listed BACnet Building Controllers application program network Each Universal Input can be configured for analog or digital input Input Output type is configured by writing to BACnet object properties MS TP Point Pickup Module...

Страница 7: ...ue Siemens operator workstation Revision 3 11 and later provide System Profile icons representing MS TP PPM devices Siemens BACnet operator workstations with BOB BACnet Object Browser available with Rev 3 7 and later provide the ability to modify the MS TP PPM s custom default device ID device name and COV increment NOTE BACnet systems consist of devices that communicate using the BACnet protocol ...

Страница 8: ...oard Diagrams 8 Siemens Industry Inc 125 5065T 2012 08 06 Board Diagrams Figure 1 6 Point Analog controller board Figure 2 6 Point Digital controller board Figure 3 12 Point Combination controller board ...

Страница 9: ...Binary Inputs Status indication voltage free dry contact 4 2 5 Counter Count accumulator voltage free dry pulse contact 3 Analog inputs w 12 bit A D resolution Temperature Ni 1000 4 4 Temperature Pt 1000 385 4 4 Temperature NTC 10K Type II 1 Voltage DC 0 to 10V 4 4 Current DC 4 to 20 mA 2 Digital outputs BO OnOff NO Contact 240 Vac 5A Resistive 2 A General Purpose 2 3 Analog outputs DC 0 to 10V 2 ...

Страница 10: ... or dry contact Digital Outputs 6 Point Digital PPMs PPM 1U32 BPR and PPM 1U32 BPF 2 Form A NO Normally Open Relays 24 to 240 Vac 5A resistive 2A General Purpose 5 2 2 Hand Off Auto switches provide manual operation of the relays for commissioning 6 Point Digital PPM PPM 1U32 BPR 12 Point Combination PPMs PPM 2U3322 BPFand PPM 2U3322 BPR 3 Form A NO Normally Open Relays 24 to 240 Vac 5A resistive ...

Страница 11: ...50 C Humidity Range 5 to 95 rh non condensing Communication RS 485 Port The RS 485 port provides a path for commands and information transmitted between field panels or other BACnet devices This port provides communications over an RS 485 BACnet MS TP The RS 485 port provides half duplex asynchronous serial RS 485 communications over shielded twisted pair cable The communication terminations netwo...

Страница 12: ...witches are available only for the Digital MS TP PPM PPM 1U32 BPR These switches can be used for commissioning In the H position the digital output is ON in the O position the digital output is OFF For system control the switch must be set to the A position Figure 4 Hand Off_Auto Switches Digital Only ...

Страница 13: ...ches 1 through 8 are used to set the MAC address Switches 9 and 10 are used to set the communication speed baud rate Figure 5 DIP Switches Baud Rate Settings Use DIP Switches 9 and 10 to set the device s communication speed baud rate Baud Rate Switch 9 Switch 10 9600 OFF OFF 19200 OFF ON 38400 ON OFF 76800 ON ON ...

Страница 14: ... Indication DO DO1 DO2 DO3 Indicates the ON OFF status of the associated DO A glowing LED indicates that the DO is energized The 6 point digital and 12 point combination controllers have two and three DOs respectively Power Receive POWER RX Indicates the power and communication status of the device Solid ON indicates device is powered no communication OFF indicates unit not powered Flashing indica...

Страница 15: ...STP network and can be adjusted down for better resolution or up for less network traffic Default COV limit is 0 5 for AI s and AO s thermistor NTC10K Ni1000 Pt1000 0 5F 0 10V or 4 20 mA 1 MaxInfoFrames is configurable from 1 to 15 the default is 12 This variable specifies the maximum number of information frames COVs the node may send before it must pass the token Accuracy Resolution Signal Accur...

Страница 16: ...emens Industry Inc 125 5065T 2012 08 06 Wiring See the Wiring Guidelines Manual 125 3002 for additional wiring information Figure 9 Power Wiring Figure 10 FLN 2 wire network interface Figure 11 FLN 3 wire interface ...

Страница 17: ...stry Inc 125 5065T 2012 08 06 I O Configuration Diagrams Figure 12 AI DI wiring for 6 point digital Figure 13 DO wiring for wiring for 6 point digital Figure 14 Analog input wiring Figure 15 Universal input wiring Figure 16 Analog output wiring ...

Страница 18: ...e an operator s terminal and the operator interface or a TALON View workstation For more information see the following documentation TALON Firmware User s Manual 588 580 It is good practice to back up the MS TP PPM While performing the troubleshooting procedures outlined in this manual you may want to refer to the device database routinely and whenever changes are made to the database or new equip...

Страница 19: ...Service Information Reinstalling the Mounting Tabs 19 Siemens Industry Inc 125 5065T 2012 08 06 NOTE The end with the screw hole slides into the channel first Figure 17 Reinstalling a DIN Mounting Tab ...

Страница 20: ... a two state signal such as ON OFF and OPEN CLOSE For example low temperature detectors differential pressure switches flow proof switches and door closures digital output DO point Point that sends a two state signal such as ON OFF and OPEN CLOSE For example two speed fan motor starters two position valves and dampers pump motor starters lighting switches and chiller and boiler switches HAND OFF A...

Страница 21: ...d diagrams 8 wiring 16 17 DIP switch 13 E electrostatic discharge ESD 18 H Hand Off Auto switches 12 I I O configuration diagrams 17 N communication network 11 compatibility 7 wiring 16 O overview 6 S service information 18 electrostatic discharge ESD 18 reinstalling the mounting tabs 18 baud rate settings 13 DIP switch 13 Hand Off Auto 12 specifications 10 status LEDs 14 DIP switches 13 Hand Off ...

Страница 22: ...hnologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel 1 847 215 1000 2012 Copyright Siemens Industry Inc Technical specifications and availability subject to change without notice Document ID 125 5065T 125 5065T AA Edition 2012 08 06 ...

Отзывы: