Communication (RS-485 Port)
11
Siemens Industry, Inc.
125-5065T
2012-08-06
Temperature Monitoring Accuracy
Operating Environment
6 Point Digital PPMs (PPM-1U32.BPR and PPM-1U32.BPF)
±1.0°F over a range of 55°F to 95°F (13°C to 35°C) PPM-1U32.BPR and PPM-
1U32.BPF
12 Point Combination PPMs (PPM-2U3322.BPFand PPM-2U3322.BPR
±1.5F over a range of 25F- 302F (-20 to 150°C)
)
6 Point Analog PPMs (PPM-2U22.BPF and PPM-2U22.BPR
±1.5F over a range of 25F- 302F (-20 to 150°C)
)
Shipping and Storage Temperature
-13°F to 158°F (-25°C to 70°C)
Operating Temperature
32°F to 122°F (0°C to 50°C)
Humidity Range
5% to 95% rh (non-condensing)
Communication (RS-485 Port)
The RS-485 port provides a path for commands and information transmitted between
field panels or other BACnet devices. This port provides communications over an RS-
485 BACnet MS/TP
The RS-485 port provides half-duplex, asynchronous serial RS-485 communications
over shielded twisted pair cable. The communication terminations (+ –
network. The communication speed is set during startup using the
DIP switch.
) are shown
on the inside unit cover.
The PPM can reside on any BACnet building controller’s sub network. Refer to other
device manufacturer’s PICs and BIBBs to determine interoperability. Up to 32 MS/TP
devices can be supported on a BACnet/IP network*.
* The MS/TP PPM is an 1/8 load device.