Document No. 155-052P25

SW 141-1

June 17, 2010

 

SW 141 Differential Static 
Airflow Switches

 

 

141-0518 

 

 

Siemens Industry, Inc. 

Description 

The SW 141 Airflow Switch senses static differential pressure and the diaphragm operated 
snap switches actuate electrical circuits. Auto reset and manual reset models are 
available. 

Application 

Auto reset switches (141-0518 and 141-0574) should be used for applications requiring 
positive proof of airflow (or fan operation) or to detect high differential pressures 
associated with dirty air filters or similar maintenance alarms not requiring safety lock-out 
(shut down) of the fan. 

The manual reset switch (141-0575) should be used for applications requiring safety lock 
out (shut down) of the fan. The switch can be used on the fan discharge (positive 
pressure), fan inlet (negative pressure), or across the fan (differential pressure) to detect 
excessively high positive pressures or low negative pressures, and turn off the fan before 
damage occurs to ducts or dampers. 

Product Numbers 

Table 1. 

Product  
Number 

Setpoint Range 

(Field Adjustable) 

Setpoint * 

Accuracy 

Switching * 

Differential 

Switching 

Action 

141-

0518 

1” to 12” WC 

(250 Pa to 3000 Pa)

@ 12” 

±

 1.5” WC 

(3000 Pa 

±

 

375

 Pa)

Approx. 

0.6” to 1.5” WC 

(150 Pa to 375 Pa)  

SPDT/ 

Auto Reset

141-

0575 

1” to 12” WC 

(250 Pa to 3000 Pa)

@ 12” 

±

 1.5” WC 

(3000 Pa 

±

 

375

 Pa)

Not Applicable 

SPST/ 

Manual 

Reset 

 

141-

0574 

0.05” to 1.0” WC 

(12.5 Pa to 250 Pa) 

@ 1”±0.2“ WC 

(250 Pa 

±

 50 Pa)

 

Approx. 

0.06

"

 to 0.6” WC 

(15 Pa to 150 Pa) 

SPDT/ 

Auto Reset

Setpoint accuracy

 tolerance

 and switching differential decrease proportional to setpoint decrease. 

Содержание Powers SW 141 Series

Страница 1: ... used for applications requiring safety lock out shut down of the fan The switch can be used on the fan discharge positive pressure fan inlet negative pressure or across the fan differential pressure to detect excessively high positive pressures or low negative pressures and turn off the fan before damage occurs to ducts or dampers Product Numbers Table 1 Product Number Setpoint Range Field Adjust...

Страница 2: ...One conduit size 1 2 inch Sample line connectors Two connectors complete with nuts and ferrules which accept 1 4 inch OD 6 4 mm copper or poly tubing Material Aluminized steel Agency certification U L MFHX File MH9888 CSA 1811M25 Weight 1 lb 0 45 kg Dimensions See Figure 9 Accessories High accuracy static pressure sensor 269 062 Static pressure sensing kit 189 142 Operation The diaphragm operates ...

Страница 3: ...ure switch Connect the highest static pressure line to the high inlet and the lowest static pressure line to the low inlet marked on the case and Figure 2 141 0518 141 0574 141 0575 Figure 2 Switches with Covers Removed Setpoint Adjustment Each switch is factory set at the minimum setpoint See Table 1 1 To increase the setpoint turn the adjustment screw clockwise as shown in Figure 2 and Figure 3 ...

Страница 4: ...he pressure inside a pipe or duct and comparing it to the air outside ambient the pipe or duct is an example of static pressure measurement A sensor measuring the pressure differential across a pump or chiller measures velocity pressure Figure 4 Pitot Tube Part Number 269 062 Wiring Diagrams Before setpoint pressure is applied to the diaphragm the switch contact is in a normally closed position as...

Страница 5: ...ve owners 2010 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Wiring Diagrams Continued Figure 8 Auto Reset Switches to Prove Insufficient Airflow or Pressure Dimensions SW000098R1 Lo...

Отзывы: