Technical Instructions

Document No. 155-314P25

EA 599-16

August 1, 2007

 

MT Series SSC Electronic 
Valve Actuator, 24 Vac  
Floating Control (3-Position) 
 
 

 

 

EA1157R1

 

 

Siemens Building Technologies, Inc. 

Description 

The Powermite 599 MT Series SSC81U and SSC81.5U electronic valve actuators 
require a 24 Vac supply to provide a floating control signal. These actuators control 
Powermite 599 MT Series valves with a 7/32-inch (5.5 mm) stroke and a threaded 
valve bonnet that fits the actuators.  

Features 

  UL listed for plenum installations 

  Direct-coupled installation without special tools (hand-tightened) 

 Manual 

override 

  Visual position indication 

Application 

The Powermite 599 Series MT Series SSC81 electronic actuators and MT Series 
valves are used in heating and cooling applications. They are used in liquid and steam 
applications that require an actuator. The SSC81 series accepts plenum cable or 3/8-
inch flex conduit connection.  

Product Numbers 

Table 1.  Product Numbers.  

Actuator Operating 

Mode 

Actuator Prefix 

Code 

SSC81U 

Non-Spring Return 

(Fail-in-Place) 

259 

SSC81.5U 

Spring Return 

(Fail-Safe) 

260 

 

Ordering a Valve 
Plus Actuator 
Assembly 

To order a complete valve plus actuator assembly from the factory, combine the 
actuator prefix code with the suffix of the valve product number. See 

Technical Bulletin 

TB251, Powermite 599 Series MT Series Terminal Unit Valve and Actuator Assembly 
Selection

 (155-306P25) for selection procedures.  

To order an actuator only, use the product number.  

Содержание Powermite 599 MT Series

Страница 1: ...ation Application The Powermite 599 Series MT Series SSC81 electronic actuators and MT Series valves are used in heating and cooling applications They are used in liquid and steam applications that require an actuator The SSC81 series accepts plenum cable or 3 8 inch flex conduit connection Product Numbers Table 1 Product Numbers Actuator Operating Mode Actuator Prefix Code SSC81U Non Spring Retur...

Страница 2: ... Functional operation Running time SSC81U 150 s 2 at 50 Hz 125 s 2 at 60 Hz SSC81 5U 125 s 2 at 50 60 Hz Spring return SSC81 5U only Figure 1 30 s Nominal stroke 7 32 inch 5 5 mm Nominal force 67 lb 300N Stroke signal relationship Linear Capacitor charge time Figure 1 max 180 sec Spring return SSC81 5U only Non mechanical electronic returns to stem up 0 position Agency certification UL UL873 Liste...

Страница 3: ...tionately to the length of time the signal is applied In the event of a power failure with no control voltage the non spring return SSC81U will hold its last position In the event of a power failure the SSC81 5U spring returns to the stem up 0 position The SSC81 5U includes an electronic return mechanism that functions as follows See Figure 1 At power up t0 a capacitor must charge to its maximum c...

Страница 4: ...onvolatile memory on the first startup of the actuator Successive startups bypass the calibration stroke unless the memory is manually cleared If installing the actuator on a different valve such as on a replacement valve manually clear the calibration stroke from memory as follows 1 Remove the terminal cover using a Phillips head screwdriver 2 Locate hole on the circuit board shorting bars 3 Inse...

Страница 5: ...ull life of the actuator Wiring Diagrams NEUT CONTROLLER ACTUATOR EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER 120 Vac 1 0 Y2 Y1 G 24 Vac EA0795R1 Y2 Retracts actuator shaft Y1 Extends actuator shaft G System potential Figure 4 SSC81U Non Spring Return EA1234R1 NEUT CONTROLLER EARTH GROUND ISOLATING CLASS 2 24 Vac TRANSFORMER 120 Vac 24 Vac ACTUATOR G Y2 Y1 G0 1 0 0 Y2 Retracts actu...

Страница 6: ... the center of the position indicator See Figure 7 CLOCKWISE EXTENDS SHAFT COUNTER CLOCKWISE RETRACTS SHAFT EA1161R1 A B A B Figure 7 Manual Override Start up Check the wiring and the position indicator Figure 8 Position Indicator Output Shaft 0 Retracted 1 Extended 0 1 EA1158R1 Figure 8 Position Indicator Shown in 0 Position Troubleshooting Check the wiring for proper connections Service Kits If ...

Страница 7: ...n may be the trademarks of their respective owners 2007 Siemens Building Technologies Inc Siemens Building Technologies Inc 1000 Deerfield Parkway Buffalo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 155 31425 Country of Origin US Page 7 Dimensions 2 48 4 4 110 8 3 5 89 85...

Отзывы: