background image

P/N 315-093312-7

P7

P5

P3

P1

P2

P4

P6

P8

PLC-4 MODULE BOARD

Circuit 1

Edge connector

Edge connector

Circuit 2

Circuit 3

Circuit 4

CB1

P1

P2

PL864-25A/70A

CB1

P1

K1

P2

PL864-25S

Figure 2

PL864 Plug-on Boards

Figure 1

PLC-4 Module Board

Installation Instructions

Model PLC-4
Power Limiting Module

INTRODUCTION

Refer to the

 MME-3 or MLE-6 Power Limited

Wiring Instructions,

 P/N 315-094883 or P/N 315-

094970, as applicable, for further information.

The Model PLC-4 from Siemens Industry, Inc.,
(See Figure 1) and its associated PL864 plug-on
boards (See Figure 2) limit the power of the
MXLV system to comply with UL-864. There are
three different PL864 boards that can plug onto
the four slots of the PLC-4:

• the PL864-25A
• the PL864-70A
• the PL864-25S

The PL864-25A and the PL864-70A plug onto
the PLC-4 to limit power to audio circuits. The
PL864-25S plugs onto the PLC-4 to limit power
to strobe circuits.

NOTE:

Use the PL-864S for strobe circuits
only. Using the PL-864S for audio
circuits may damage the system.

Use the PL864-70A for 70.7V audio
circuits only.

The PLC-4 plugs onto one of the OMM card
edge connectors. A single PLC-4 with four
PL864 plug-on boards can serve up to four
audio and/or strobe circuits.

The PLC-4 and PL864-25A/70A audio cards do
not supervise themselves. However, since all
audio power to the MXLV system passes
through them, signal losses appear as troubles
for the ASC-1/2 modules.

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Содержание PLC-4

Страница 1: ...e PLC 4 the PL864 25A the PL864 70A the PL864 25S The PL864 25A and the PL864 70A plug onto the PLC 4 to limit power to audio circuits The PL864 25S plugs onto the PLC 4 to limit power to strobe circuits NOTE Use the PL 864S for strobe circuits only Using the PL 864S for audio circuits may damage the system Use the PL864 70A for 70 7V audio circuits only The PLC 4 plugs onto one of the OMM card ed...

Страница 2: ...to either the CSM 4 or MMB b Determine which circuits will be used Refer to Figure 1 for the location of the circuits on the PLC 4 board and to Figure 5 for circuit wiring c Remove the PLC 4 card from its protec tive bag d Remove the PL864 25A PL864 25S or PL864 70A cards from their protective bags e Place the PL864 plug on cards one at a time over the connectors on the PLC 4 card for the desired ...

Страница 3: ...s kept at right angles to the OMM board Otherwise the plug in card can damage or displace other components Wiring Refer to Figure 5 All wiring must comply with national and local codes Dress the leads properly Maintain the proper routing and distances between the wiring that is power limited terminals 15 22 and wiring that is not power limited terminals 1 8 Refer to the MME 3 or MLE 6 Power Limite...

Страница 4: ...TIONS CONNECT TO CLOSURE MONITORING DEVICE CONNECT TO CLOSURE MONITORING DEVICE AUDIO FROM AMPLIFIER AUDIO TO ASC 1 OR ASC 2 AMPLIFIER INPUT AUDIO FROM AMPLIFIER AUDIO TO ASC 1 OR ASC 2 AMPLIFIER INPUT CIRCUIT 2 IN 24 VOLTS TO ZC1 8B STROBE CARD INPUT 24 VOLTS FROM MMB PSR 1 OR ANY UL LISTED POWER SUPPLY MANUFACTURED BY ALARM SAF MODEL BN4 002 UL 24 VOLTS FROM MMB PSR 1 OR ANY UL LISTED POWER SUPP...

Отзывы: