38/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device addresses via ACS
30.08.2007
5.2
RM… controller device address
The Synco 700 devices are factory-set with device address 255. This address must
be changed to allow communication via the KNX bus. The address can be modified
in different ways with ACS Service (see further below).
For information about the various RM… controllers, refer to the associated data
sheets and basic description documents (for details see section 1.2).
The RM… controllers can supply power to the KNX bus.
For communication purposes, the RM… controllers can be operated with the
setting "Decentral bus power supply = On". Alternatively a central bus power
supply must be available (see section 2.2).
5.2.1
Assigning addresses manually
With ACS service and manually assigned addresses, the Synco 700 devices,
RXB/RXL room controllers, OZW77x central communication units and Synco 900
type QAX910 central apartment units can be allocated a device address and a
device name.
1.
In ACS Service select
Plant > Edit device list…
to open the "Edit device list" dialog
box.
2. Select the required device with the left mouse button.
3. Click
Manually…
to open the "Address assignment" dialog box.
4. Enter a device address in the range 1…253 (excluding 150), and confirm by
clicking the
Write
button.
Introduction
Note
Bus power supply
Procedure