30 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Commissioning
28.08.2012
2.5.3
Operating page settings "Message recipient"
You can define time periods for each message recipient when messages can
be sent.
•
The following settings are optional if you want to limit the time periods when
messages can be sent (default: no time limit).
•
General: Messages outside sending periods are resubmitted if they are still
pending during the sending period.
Path: Home > 0.5 OZW672… > Message receiver > Message receiver 1…4 >
Send messages
You can define time periods per weekday or special day when messages can be
sent to the message recipients.
Special days are defined via
Holidays/special days
.
Data point
Explanation, example
Monday...Sunday,
Special day
Default val: Monday
00:00
On
…
Special
day
00:00
On
…
Setting val:
Monday...Sunday,
Special
day
00:00…24:00
Off
/
On
Max 3 sending periods can be defined when
web servers can send messages for each
weekday and special day(s). The previous
day's status is transferred to the current day.
The default settings is to always send mes-
sages.
•
Check
to enable switching points.
•
You can copy the switching times for a day of the week by
clicking [ Copy ] one day to a selection of other days .
•
Click [ Check ] to check the data before it is saved.
Message receiver
Notes
Send messages
Notes