2.9 Final
steps
2.9.1
Check faults
The fault indicator displays the plant state.
Fault indicator
No faults may be pending after commissioning. Additional information on faults is
available in Section 3.3.
Note
No fault
The fault indicator remains green as long as no fault is pending.
Fault
The fault indicator changes to red for faults.
The most severe plant faults are displayed:
•
Device name
•
Fault text
2.9.2
Final steps on web server
The final function checks are conducted on the web server, the cover is mounted
and the LEDs checked.
Final tasks
On display and operating elements, see Section 1.2.
Note
Procedure:
1.
Unplug USB cable.
2.
Switch off message suppression:
– Remove the cover.
– Message suppression switch (
8
) must be on "Off"
.
3.
OZS164.23 only: The SIM card is inserted.
4.
Mount terminal cover.
5. Press
Remote (
6
) button for more than 6 seconds.
– The web server sends a system report to the defined message recipients.
– Fault LED (
4
) displays (flashing) error in establishing communications.
6. LED
On must be steady green.
7.
Fault LED must be dark.
45 / 108
Siemens Web
server
CE1C5711en
Building Technologies
Commissioning
25.08.2010