Planning
4
Parameter sets for collective operation
41
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
4.4 Parameter sets for collective operation
In collective operation, the following parameter sets can be selected in the point
detector:
l
Sensitive, DOO emulation
l
A1R, DT emulation
l
BR, DT emulation
A parameter set is selected by omitting or installing a resistor with a specified value
from/at the connection terminals for the external alarm indicator in the detector
base.
+
-
+
-
+
-
R
Resistor at terminals for connecting an external alarm indicator
When the detector line is being commissioned, the LED for the internal alarm
indicator in the point detector flashes for a period of 3 minutes to show the set
parameter set.
The following table provides an overview of the resistances with which a specific
parameter set can be set:
Parameter set
Resistance value R
Flashing pattern of
internal alarm indicator
after commissioning
Sensitive, DOO emulation
∞
(no resistor installed)
Once every 6 s
A1R, DT emulation
18 k
Ω
, min. 200 mW
Twice every 6 s
BR, DT emulation
10 k
Ω
, min. 200 mW
Three times every 8 s
4.4.1 Replacing existing AlgoRex point detectors
The point detector OOH740-A9-Ex can replace a range of point detectors from the
AlgoRex range. The following table provides an overview of which parameter set
needs to be set in order to replace a particular detector type.
Point detector to be
replaced
Parameter set to be
selected
Required resistance
DO1101A-Ex
Sensitive, DOO emulation
∞
(no resistor installed)
DT1101A-Ex
A1R, DT emulation
18 k
Ω
DT1102A-Ex
BR, DT emulation
10 k
Ω