Operating the switch-disconnector panel
226
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fit a padlock (optional) to the operating slide and close it.
✓
The switch-fuse combination has been operated from CLOSED position to OPEN position.
18.8 Operating lever for earthing switch
Operating lever for earthing switch:
•
With the operating lever, the switching process at the feeder earthing switch can only be executed in
turning direction.
•
The turning movement into the opposite direction has a freewheel and does not move the feeder
earthing switch; the operating lever works like a ratchet spanner.
•
The feeder earthing switch is operated either clockwise or counter-clockwise according to the
switching function.
•
To use the operating lever, two instruction labels show the turning direction for the corresponding
switching function.
Switching function:
From OPEN to CLOSED position From CLOSED to OPEN position
Turning direction of the
operating lever:
Clockwise
Counter-clockwise
Instruction label on
the
operating lever:
Fig. 402: Instruction labels on the operating lever