NXAIR /
≤ 40 kA
110-0134.9 / 13
Operating the busbar connection panel type I
15 Operating the busbar connection panel type I
INFORMATION
Read and understand these instructions before attempting operating works.
15.1 Control elements at the front side of the panel
(1) Door to the low-voltage compartment
(2) Protection device
(3)
Locking device for the door to the low-voltage
compartment
(4) Instruction label for closing the high-voltage door
(5) Handle for opening the high-voltage door
(6)
Actuating opening for inserting the double-bit key to
control racking of the withdrawable
metering part / metering truck
(7)
Mechanical position indicator for withdrawable
metering part / metering truck
(8) High-voltage door
(9)
Actuating opening for racking the withdrawable
metering part / metering truck
(10)
Operating slide for opening and closing the
actuating opening for racking the withdrawable
metering part / metering truck
(11)
Test sockets for busbar voltage detecting system
(type LRM) as additional component
Fig. 363: Control elements on
the panel front
15.2 Position indicator visible on high-voltage door
Indicator for position of withdrawable metering part
/
metering truck:
Position indications for:
Service position
Intermediate position
Test position