Automation level configurations
64
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
Routing and firewall options:
–
Stand-alone firewall:
–
Protection from external sabotage
–
Routing between Ethernet 1 and Ethernet 2 disabled
–
Edge firewall:
–
Protection of internal network (e.g. MM8000 connected to FS20) with
specific port access to external network (e.g. Modbus client via NK823x)
–
Routing between Ethernet 1 and Ethernet 2 enabled
–
Edge firewall advanced:
–
Traffic from external network can be filtered by source/destination (IP
addresses configurable)
–
Custom ports configurable
–
Relay output diagnostics:
- ETH1/ETH2 cable disconnected
- NK823x failures (low memory, logging failed, and SW error)
–
Router:
–
The routing between ETH1 and ETH2 can be enabled / disabled
–
Static routing with routing tables
–
Dynamic routing with Open Shortest Path protocol (OSPF)
3.3.3.2 Subsystems connected via RS232 interface
Fig. 38 Example of subsystems connected via RS232 interface