6AW5451-6XX01-1K
ES 030-K Manual
Subject to change without prior notice
6 - 3
RD: 08.2000
(4)J31069-D0136-U001-A0-7618
6.2.2
Test Mode
The test mode serves to test the user software by means of
breakpoints. The program will be halted at those points at
which a NOP 1 has been programmed. The user can then
check and alter the status of E, A, M, etc.
Entering the Test Mode
- Connect mains connector while pressing test mode switch
(Key 1 to the upper left), with key switch in the horizontal
position.
- Set flag 2.0 in the user program.
H W - T E S T E S 0 3 0 - K V 0 3 9 4
E X T E R N A L R A M X X K O K
System message:
(does not appear when setting flag 2.0)
Press DUE key
H A R D W A R E T E S T N U M B E R
O R 0 = D O W N L O A D ?
System message:
(does not appear when setting flag 2.0)
Press due key
System message:
B R E A K P O I N T : XXXX
yy : zz
xxxx is the address of the next PG program printout
(hexadecimal) command to be processed.
yy = block type (FB or OB)
zz = block number (hexadecimal indication)
Working in the Test Mode
By pressing the SPR key (see Chapter 6.2.1) while the key
switch is in the vertical position, it is possible to jump from
NOP1 to NOP1, when the key switch is in the horizontal
position, from command to command.
Leaving the Test Mode
Disconnect and re-connect mains connector.
(Set flag 2.0 must be reset by the user).