6AW5451-6XX01-1K
ES 030-K Manual
3 - 4
Subject to change without prior notice
RD: 08.2000
(4)J31069-D0136-U001-A0-7618
3.2.1.1 DL 2 Switch 1 on the Motherboard
Bit 7 6 5 4 3 2 1 0
Available for parameterization by user
Without keyboard, bit 7 is used to switch to download mode on ON and voltage return
3.2.1.2 DL 41, DL 47 Baud Rate, Procedure Parameter
Bit 7 6 5 4 3 2 1 0
Baud rate
1 = 150 Baud
5 = 2400 Baud
2 = 300 Baud
6 = 4800 Baud
3 = 600 Baud
7 = 9600 Baud
4 = 1200 Baud
8 = 19200 Baud
0/1
8/7 data bit
0/1 odd/even
parity
0/1
1/2 stop bit
3.2.1.3 DL 41 for SINEC L1 Address
Bit 7 6 5 4 3 2 1 0
0
= ES 030 is master
Control carried out via FY 18 and FY 19.
1
= Reserved for the ES 030 master terminal
The master terminal (Addr. = 0) is simultaneously the slave
terminal with address = 1.
2 - 30 = Address of the ES 030 as slave
3.2.1.4 DR 41 Driver Standard Interface
Bit 7 6 5 4 3 2 1 0
Driver 0 = no
driver
2 = 3964R
procedure
1 = LAUF procedure
3 = SINEC L1
0/1
master/slave on 3964R
0/1
XON/XOFF off/on (only with LAUF and transmit)
0/1
Extended buffer length off/on (only on 3964R)
3.2.1.5 DR 47 Driver Expansion Interface
Bit 7 6 5 4 3 2 1 0
Driver
0 = no driver
3 = no driver
1 = LAUF procedure
4 = PREMID (always with expanded
2 = 3964R procedure
buffer length; setting bit 5 is not
required)
0/1
master/slave on 3964R
0/1
XON/XOFF off/on (only with LAUF and transmit)
0/1
Extended buffer length off/on for LAUF driver
0/1
Checksum off/on for LAUF driver