Siemens MKB-5 Скачать руководство пользователя страница 1

Separate 

UP

 and 

DOWN 

keys located next to the

MORE INFO

 key allow the user to scroll forward and

backwards through the entire list of events.

The 

SPACE 

key allows the user to input addresses

faster by enabling them to reduce redundant  key
presses of the “0” key.

The 

MORE INFO

 key allows the user to instantly view

all relevant information about the highlighted event,
which is displayed in the last three lines of the screen.

The user can access the MXL Control menu by
pressing the 

ENTER 

key.

The panel has System status indicator LEDs. The

ALARM 

and 

TROUBLE

 LEDs function even if the

main processor fails. (See Figure 1).

Installation Instructions

Model MKB-5/-5C
Annunciator/Keypad Module

The Model MKB-5/-5C Annunciator from Siemens
Industry, Inc., communicates with the MMB Main
Control Board through the System network link. The
MKB-5/-5C provides the MXL with its primary control
and annunciation.

OPERATION

The MKB-5/-5C has a multi-line display that continu-
ously updates information about the system event
status. If there are multiple events (alarms, security
conditions, supervisories and/or troubles), the highest
priority event that occurred displays on the screen. The
user can view up to 8 events at a time and can scroll

through the complete list using the Up (

) and Down

(

) keys located next to the More Info key. For further

information on the operation of the MXL Multi-Line
Keyboard/Display Panel, refer to the MXL Keyboard/
Display Panel Operating Instructions, P/N 315-048692,
and Section 3, OPERATION, in the 

MXL/MXLV

Manual, 

P/N 315-092036.

The keyboard/display panel has keys for the following
functions:

• Acknowledging fire alarms 

(ALARM ACK)

• Silencing audibles 

(AUD SIL)

• Acknowledging supervisories 

(SUPV ACK)

• Acknowledging troubles 

(TRBL ACK)

• Acknowledging security conditions 

(SEC ACK)

There is also a separate key for resetting the Control
Panel 

(RESET).

The 10-digit numeric keypad allows entry of the three
levels of user passwords. It is also used to perform
specific menu-driven operations as well as pro-
gramming and maintenance functions.

Figure 1

MKB-5/-5C Panel

SUPV

ACK

ACK

ALARM

SIL

AUD

DISABLED

PARTIAL SYSTEM

POWER

ACK

TRBL

ACK

SEC

RESET

ALT 1

FUNCTION

FUNCTION

ALT 2

FUNCTION

MORE

INFO

4

*

7

PQRS

GHI

8

9

0

#

5

TUV

JKL

6

WXYZ

MNO

1

2

ABC

3

DEF

ALT

ENTER

CLEAR

SPACE

PRINT

ALT

2

F4

1

F3

F2

HELP

F1

P/N 315-048727-5

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Содержание MKB-5

Страница 1: ... on the screen The user can view up to 8 events at a time and can scroll through the complete list using the Up and Down keys located next to the More Info key For further information on the operation of the MXL Multi Line Keyboard Display Panel refer to the MXL Keyboard Display Panel Operating Instructions P N 315 048692 and Section 3 OPERATION in the MXL MXLV Manual P N 315 092036 The keyboard d...

Страница 2: ... address 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 J3 J10 J11 S1 S2 S3 J12 J4 J2 J1 J5 _ TO OPTION MODULES TO OPTION MODULES LCD KEYBOARD LEDS BACKLIGHT SERIAL PRINTER SERIAL PRINTER PARALLEL PRINTER PARALLEL PRINTER 1 1 1 2 1 1 VR1 CONTRAST VR2 BRIGHTNESS BRIGHTNESS J6 J7 J9 J13 J8 1 2 3 4 5 1 2 3 4 5 NETWORK 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 S1 S2 S3 A...

Страница 3: ... plugs are in place on J13fornormaloperationandnetworkprogramming 6 Using8 wireribboncableP N555 148722 connect J4 on the back of the MKB 5 5C to P6 on the MMB or to P7 or P10 on the MOM or to P3 or P4 on the OMM Make sure that the red tracing wire is at position 1 on both connectors 7 If the MKB 5 5C is used with an MXLV system connect P5 on the ACM 1 to P8 on the MMB 2 3 8 Refer to MMB 3 Install...

Страница 4: ...ification for MXL MXL IQ and MXLV Systems P N 315 092772 revision 6 or higher for additional wiring information 11 Maximum voltage 8V peak to peak Maximum current 150mA P N315 048727 5 Figure 6 Typical Style 7 Wiring MMB 3 Notes 1 Use a minimum wire gauge of 22 AWG 2 Use a maximum of 80 ohms per pair of wires for the network connections 3 Use shielded twisted pair for network connections 4 Termina...

Отзывы: