P635 Verification Totalizer
Enables a dedicated internal totalizer that totals the amount of material conveyed during
a zero or span verification. It is used to verify the accuracy of the scale.
If a printer is connected to a port and the required programming is in order, a printout of
the activity is automatically done on completion of the verification process.
Entry:
0 = OFF, verification totalizer disabled
f
1 = do not total, verification totalizer is enabled, but main totalizers* are disabled
2 = add total, verification totalizer is enabled as well as main totalizers*
*main totalizers consist of internal totalizers 1 and 2, and external totalizers
1 and 2.
P638 External Totalizer Resolution
This parameter sets the resolution of the selected external totalizer.
Totalizers are:
P638-01, external totalizer 1 (T1), terminals 35/36
P638-02, external totalizer 2 (T2), terminals 38/39
Entry:
1 = 0.001 (one thousandth)
2 = 0.01 (one hundredth)
3 = 0.1 (one tenth)
4 = 1 (unit)
f
5 = 10 (x ten)
6 = 100 (x hundred)
7 = 1000 (x thousand)
Note:
If the resolution selected would cause the totalizer to lag behind the
count at 100% of design rate, the next possible resolution is automatically
entered.