Page 102
Milltronics SF 500 - INSTRUCTION MANUAL
7ML19985CN01
mmmm
m
Pa
ra
m
et
er
s
9 = PID freeze
10 = PID setpoint source
11 = PID mode
12 = external alarm
13 = remote communication write
14 = Initiate On-line Calibration
15 = Accept new on-line calibration span**
*If the SF 500 is programmed for multispan operation, the auxiliary input contact state
determines the multispan number (equivalent to P365). Input 1 is reserved for multispan 1
and 2 selection. Input 2 is reserved for multispan 3 and 4 selection, and Input 3 for 5 to 8.
** Enter 1 (existing ALT_DSP) to reject the new on-line calibration span.
Calibration Parameters (P295 – 360)
P295 Load Cell Balancing
Initiates an electronic balancing of the load cell input signals. Balancing is required for
flowmeter models of two-load cell design.
Refer to
Start Up
on page 23 for requirements and execution.
P341 Days Of Service
The cumulative days that the application device has been in service. The time is recorded
once daily in a non-resetable counter. Periods of less than 24 hours. are not recorded, nor
accumulated. (
f
= 0)
Multispan
selection
Auxiliary Input 1 Auxiliary Input 2 Auxiliary Input 3
1
2
3
4
5
6
7
8