8. SPECIFICATIONS
G85139-H1751-U529-D1
© Siemens plc 1999
4/8/99
70
Input frequency:
47 Hz to 63 Hz
Mains supply impedance:
> 1% (fit input choke if < 1%)
Power factor:
³
0.7
Output frequency range:
0 Hz to 650 Hz
Resolution:
0.01 Hz
Overload capability:
200% for 3 s and then 150% for 60 s (related to nominal current)
Protection against:
Inverter overtemperature.
Overvoltage and undervoltage
Additional protection:
Against short-circuits and earth/ground faults pull-out protection.
Protection against running with no load (open-circuit)
Operating mode:
4 quadrants possible.( Re-generation back into mains not possible ).
Regulation and control:
Sensorless vector; FCC (Flux Current Control); voltage/frequency curve;
Analogue input / PID input:
Unipolar: 0 ~ 10 V/ 2 ~ 10 V (recommended potentiometer 4.7 k
W
)
0 ~ 20 mA/ 4 ~ 20 mA
Bipolar: -10 ~ 0 ~ +10V
Analogue setpoint resolution:
10-bit
Analogue output:
0 - 20 mA/4 - 20 mA @ 0 - 500
W
; stability 5%
Setpoint stability:
Analogue < 1%
Digital < 0.02%
Motor temperature monitoring:
PTC input, l
2
t control
Ramp times:
0 - 650 s
Control outputs:
2 relays 230 V AC / 0.8 A (overvoltage cat.2); 30 V DC / 2 A
WARNING:
External inductive loads must be suppressed
(see section 1.2)
Interface:
RS485
Inverter efficiency:
97%
Operating temperature:
0
o
C to +50
o
C (MMV), 0
o
C to +40
o
C (MDV)
Storage/transport temperature:
-40
o
C to +70
o
C
Ventilation:
Fan cooling (software controlled)
Humidity:
95% non-condensing
Installation height above sea level:
< 1000 m
Degree of protection:
MMV: IP20 (NEMA 1) (National Electrical Manufacturers' Association)
MDV: IP21 (NEMA 1) and IP56 (NEMA 4/12)
Protective separation of circuits:
Double insulation or protective screening.
Electromagnetic compatibility (EMC):
See section 9.3
Comment:
MICROMASTER Vector and MIDIMASTER Vector are designed for use worldwide and therefore for wide line supply voltage ranges (1/3-ph. 208 - 240
V AC ±10%; 3-ph. 380 - 500 V AC ±10%; 3-ph. 525 - 575V AC ±15%)
For the voltage data, it should be noted that:
-
the operating range of the drive inverter lies between the two specified voltage values - e.g. 208 - 240V,
-
the ±10% does not represent an operating range but only the range which is provided to absorb brief voltage fluctuations.