Pulse Inputs
MD-12HD meters are equipped with 4 pulse inputs and MD-48HD meters (hardware version I) are
equipped with two pulse inputs. Pulse counting supports accumulation of consumption data from any
external meter using a dry contact (Form A Relay) or open collector outputs. The MD-xxHD pulse inputs
are compatible with “low speed” meters. The pulse duration must exceed 50mS in both the logic low and
high state allowing for a maximum input frequency of 10 Hz.
Pulse scaling, resetting and
accumulated values are accessed through registers and are “system” in
scope. See the register list, ViewPoint HD, or videos for more information.
ALARM (SPDT)
The MD-xxHD meter supports user-configurable alarms for over-current, under-current, over-voltage, and
under-voltage. ViewPoint HD helps users set these values by allowing for values to be entered using
direct entry mode or specifying the limits as a percentage of nominal.
Alarm persistence settings are used to allow for temporary conditions, such as a motor starting, that are
beyond trigger limits. For example, in the case of meter upset from ESD events, short persistence
settings may lead to false alarm triggers. When any alarm condition has been satisfied throughout the
persistence interval, the MD-xxHD trips the MASTER ALARM relay, which is an electromechanical relay
on the PCB.
Once tripped, the relay can only be reset by clearing the alarm through Modbus register/BACnet object
2451”
The Master Alarm relay can be hard wired to an interrupt or polling circuit in a host system allowing for a
more rapid response than the data polling frequency, if desired. The status of each alarm is determined
by reading status registers. See the register list, ViewPoint HD, or instructional videos for more
information.
>50 mec
>50 mec
Note: The Master Alarm relay is intended for low voltage DC connections.
The user must protect the switch from over-current conditions when closed.
Содержание MD-12HD
Страница 1: ...ii Siemens Industry Inc User Guide MD 12HD MD 48HD Networked Metering Systems A6V11564207 ...
Страница 2: ......
Страница 9: ...Siemens Industry inc 8 Alternate Product Configuration MD 12HD C D N Enclosure with Cover Removed ...
Страница 27: ...Siemens Industry inc 26 Configuring Electrical Components using ViewPoint HD ...
Страница 68: ...67 Siemens Industry Inc Menu Navigation ...
Страница 69: ...Siemens Industry inc 68 Communication Navigation ...