LOGO! functions
4.4 Special functions list - SF
LOGO!
Manual, 04/2011, A5E03556174-01
251
4.4.29
Analog Ramp
Short description
The Analog Ramp instruction allows the output to be changed from the current level to the
selected level at a specified rate.
Symbol in LOGO!
Wiring
Description
Input En
A change in the status from 0 to 1 at input En
(Enable) applies the start/stop level (Offset "B" +
StSp) to the output for 100 ms and starts the ramp
operation to the selected level.
A change in the status from 1 to 0 immediately sets
the current level to Offset "B", which makes output
AQ equal to 0.
Input Sel
SeI = 0: Level 1 is selected
SeI = 1: Level 2 is selected
A change in status of Sel causes the current level to
start changing to the selected level at the specified
rate.
$ᇄ
$4
(Q
6HO
6W
3DU
Input St
A change in the status from 0 to 1 at input St
(Decelerated Stop) causes the current level to
decrease at a constant rate until the start/stop level
(Offset "B" + StSp) is reached. The start/stop level is
maintained for 100ms and then the current level is set
to Offset "B", which makes output AQ equal to 0.
Содержание LOGO!
Страница 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Страница 136: ...Programming LOGO 3 9 Memory space and circuit program size LOGO 136 Manual 04 2011 A5E03556174 01 ...
Страница 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Страница 302: ...Configuring LOGO 7 2 Setting the default values for LOGO LOGO 302 Manual 04 2011 A5E03556174 01 ...
Страница 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Страница 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Страница 400: ...Safety instructions 2 3 Notes about usage Basic Panels 28 Operating Instructions 04 2012 A5E02421799 03 ...
Страница 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...