LOGO! Manual
A5E00067781 01
4.4.17
Analog Trigger
Brief description
The output is switched on, if the analog value exceeds a
parameterizable on threshold. The output is switched off if
the analog value falls below the parameterizable off thresh-
old (hysteresis).
Symbol in
LOGO!
Connection
Description
Input Ax
At the output Ax, apply the
analog signal to be evalu-
ated.
Use the connectors I7 (AI1)
or I8 (AI2).
0-10 V corresponds to
0-1000 (internal value).
Parameter Par:
,
, SW
,
SW
: Gain in %
Value range 0..1000 %
: Offset
Value range
999
SW
: on threshold
Value range
19990
SW
: off threshold
Value range
19990
Output Q
Q is set or reset depending
on the threshold values.
Gain and Offset parameters
Refer to the information in Section 4.3.6 on the Gain and
Offset parameters.