
LMV Series
Technical Instructions
LV5-1000
Menu Path
Parameter
Default
Range
Description
51.1
52.2
52.4
LEGEND -
Password Access:
(U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
SD_Stage3Off (U)
6%
0-50%
Determines what temp. / press. a staged oil burner will disengage stage 3. Set at a positive %
so that the boiler will turn off stage 3 oil at a set % above the current setpoint. Percentage
based on current setpoint.
x x x
ThreshStage2On (U)
300
0-1000
This value is the integral of a control deviation multiplied by time. This serves to not call on
stage 2 unless the pressure / temperature deviates from the desired setpoint for a length of
time and/or by a large margin.
x x x
ThreshStage3On (U)
600
0-1000
This value is the integral of a control deviation multiplied by time. This serves to not call on
stage 3 unless the pressure / temperature deviates from the desired setpoint for a length of
time and/or by a large margin.
x x x
TL_ThreshOff (S)
203 F
32-3632 F
Temperature limiter function. If a temperature sensor is used (connected to INPUT X60), this
parameter controls at what temperature the burner goes into alarm and shuts down due to
an over-temperature situation.
The LMV5 locks out. The LMV5 can only be reset when the temperature goes below
TL_SD_On
. Not applicable for steam boilers.
x x x
TL_SD_On (S)
-5%
-50-0%
Creates a negative deadband for the temperature limiter function. If the temperature
reaches the threshold off value (
TL_ThreshOff
), the burner will shut off with an alarm. This
setting controls what temperature under the threshold off value the burner can be restarted.
Not applicable to steam boilers.
x x x
ColdStartOn (S)
deact
activated
deactivated
Activates or deactivates cold start thermal shock protection (low fire hold), based on temp.
or press. for a steam boiler, and temp. for a hot water boiler.
x x x
ThresholdOn (S)
20%
0-100%
This is the temp. / press. below which cold start will engage. Above this temp. /press. the
cold start will not engage. The value is a percentage of the current setpoint.
x x x
StageLoad (S)
15%
0-100%
This sets the % load of the "load step" for a stepping cold start. If the burner is to be held at
low fire (low fire hold) until the
ThresholdOff
value is reached, set at 0%.
x x x
StageSetp_Mod (S)
5%
1-100%
For modulating burners, this is how much the temp. / press. must increase before the next
load step is triggered. This is a percentage of the current setpoint. Can be set to 100% if a
burner is to be stepped by time only.
x x x
StageSetp_Stage (S)
5%
1-100%
For staged burners, this is how much the temp. / press. must increase before the next burner
stage is released. This is a percentage of the current setpoint. Can be set to 100% if a burner
is to be stepped by time only.
x x x
Params & Display>
LoadController>
TempLimiter
Params & Display>
LoadController>
ColdStart
Params & Display>
LoadController>
ControllerParam
SCC Inc.
Page 31
Section 3
HOME
HOME
P - LIST
Содержание LMV 5 Series
Страница 2: ...Intentionally Left Blank ...
Страница 25: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 1 Intentionally Left Blank HOME ...
Страница 27: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 23 Section 1 Intentionally Left Blank HOME ...
Страница 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Страница 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Страница 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Страница 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Страница 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Страница 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Страница 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Страница 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Страница 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Страница 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Страница 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Страница 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Страница 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Страница 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Страница 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Страница 56: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 22 SCC Inc Intentionally Left Blank HOME ...
Страница 116: ...Technical Instructions LMV Series Document No LV5 1000 Section 3 Page 58 SCC Inc Intentionally Left Blank HOME ...
Страница 150: ...Technical Instructions LMV Series Document No LV5 1000 Section 4 Page 32 SCC Inc Intentionally Left Blank HOME ...
Страница 170: ...Technical Instructions LMV Series Document No LV5 1000 Section 5 Page 18 SCC Inc Intentionally Left Blank HOME ...
Страница 290: ...Technical Instructions LMV Series Document No LV5 1000 Section 8 Page 20 SCC Inc Intentionally Left Blank HOME ...
Страница 306: ...Technical Instructions LMV Series Document No LV5 1000 Section 9 Page 14 SCC Inc Intentionally Left Blank HOME ...
Страница 373: ...Intentionally Left Blank ...