Technical Instructions

Document No. 7451US

LFL...

Rev. 2 November 15, 2004

 

 

 

 

LFL 

Series 

Burner Flame Safeguard Control 

 

 

 

 

The LFL… is a compact electro-mechanical
primary flame safeguard control designed to
provide burner sequencing, automatic igni-
tion and continuous flame monitoring for
gas, oil, and dual fuel, single burner applica-
tions.   
 
The LFL… is applicable for on-off, multi-
stage or modulating burners. The LFL… is
designed for direct main burner ignition, 
intermittent or interrupted pilot operation.  
 
The LFL… integrates the flame amplifier,
purge timer and sequencer in a single con-
trol. Flame supervision is accomplished
using UV sensor or flame rod detection. 
 

 

 

 

 

 

 

 

 

 

 

 

Features 
 

• 

Primary flame safeguard control 

• 

Visual sequence indication 

• 

Optional combustion air blower control 

• 

Optional postpurge 

• 

Preignition interlock 

• 

Continuous flame monitoring,  

 

including extraneous light detection 

• 

UV sensor functional test 

• 

Proven air switch function 

• 

Proven high fire purge interlock 

• 

Proven low fire ignition interlock 

• 

Direct main burner ignition,  

 

intermittent or interrupted pilot operation 

• 

Integrated flame amplifier  

• 

UV sensor or flame rod detector 

• 

Lockout alarm terminal 

• 

Local and optional remote reset  

• 

Burner off – economy position  

 

(fully closed air damper interlock) 

• 

Unit fuse and spare fuse provided 

 

 

 

 

Contents 

 

Control Interface ................................................. 2 

Installation........................................................... 2 

Ordering information ........................................... 3 

Wiring base ......................................................... 3 

Specifications ..................................................... 4 

Specifications continued ..................................... 5 

Description of oper controls ................................ 6 

Ladder diagram external connections ................. 7 

Sequence Dial OPERATION .............................. 8 

Sequence Dial FAULT and LOCKOUT ............... 9 

Sequence Chart ................................................ 10 

Dimensions ....................................................... 11 

 

 

 

 

 

 

 

 

 
 
 

 
11.15.2004 

Siemens Building Technologies

HVAC Products

 

Содержание LFL Series

Страница 1: ...nce indication Optional combustion air blower control Optional postpurge Preignition interlock Continuous flame monitoring including extraneous light detection UV sensor functional test Proven air switch function Proven high fire purge interlock Proven low fire ignition interlock Direct main burner ignition intermittent or interrupted pilot operation Integrated flame amplifier UV sensor or flame r...

Страница 2: ...nt in the sequence where the fault occurred The LFL sequence is fixed and cannot be manually manipulated Installation All installation and commissioning work must be performed by qualified personnel The LFL must be mounted in an electrical enclosure typically in the control panel All wiring must comply with applicable electrical codes standards and regulations Before performing any wiring to the L...

Страница 3: ... 12 sec 15 sec 12 sec Flame failure response time FFRT 1 sec All times listed above are for 60 Hz operation Times for 50 Hz operation will be 20 longer Description Product Number LFL Control unit Refer to Table 1 above without wiring base Wiring base AGM410490550 Flame sensor UV shown QRA 4 U forward looking 3 4 NPT UV Refer to QRA2 QRA10 Technical Instruction 7712 Flame rod By others Wiring Base ...

Страница 4: ...former 4 A Terminal 17 Pilot fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 18 Main fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 19 Main fuel valve Motor 4 FLA 24 LRA or 1 6 A pilot duty Terminal 20 Damper actuator N A Terminal ratings 110V UL File MH26134 Standard UL372 CSA Certificate 1370843 Standard CAN CSA C22 2 No 199 M89 FM File J I 3003560 Standard FM7610 110V 220...

Страница 5: ...duit from all other wiring Unshielded wire Shielded cable shield grounded to terminal 22 max 250 ft max 500 ft Flame supervision with Flame rod Electrical connection notes for flame supervision It is important to minimize electrical disturbance and signal loss Run flame signal wiring separate from all other wiring Observe the length of detector cable as indicated above The flame rod does not provi...

Страница 6: ... two options LFL output 7 M2 powered after a 2 sec delay and continues through postpurge LFL output 6 M1 powered immediately and stops prior to postpurge The combustion air switch CAS is used to prove that combustion air is being provided Most burner boiler insurance codes require a CAS Combustion air switch CAS LFL input 14 COMBUSTION AIR PROVE is connected to the normally open NO terminal of the...

Страница 7: ...Wiring Diagram 7 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Страница 8: ...Sequence dial OPERATION 2 1 P P P P P P P 8 12 Siemens Building Technologies HVAC Products 1 1 2 1 P 2 1 1 2 2 11 15 2004 ...

Страница 9: ...Sequence dial FAULT and LOCKOUT indication 1 P 2 P P P P 2 P 1 2 1 P P 1 2 2 1 1 9 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Страница 10: ...URE RELEASE TO MOD NOT USED FLAME SIGNAL COMBUSTION AIR BLOWER CLOSE MINIMUM ECONOMY FULLY CLOSED P OPEN Modulation 1 2 MTFI PTFI IDLE 19 22 23 24 18 16 17 PILOT IGNITION POSTPURGE ACTUATOR 20 11 10 9 OPEN PROGRAM SEQUENCE CHART START PREPURGE P Required INPUT Allowed INPUT 1 1 2 5 8 6 7 12 13 14 POSTPURGE 4 15 21 3 2 RESET ALARM Output ON Powered NOT Allowed INPUT Output OFF N A 10 12 Siemens Bui...

Страница 11: ...mm 3 16 x 1 4 7 16 4 3 5 8 0 3 5 8 7 16 1 7 16 4 4 mm Ø 3 16 Ø Ground Ø5 16 Ø7 5 mm 5 5 8 0 4 1 3 8 5 8 0 4 0 1 5 16 2 11 16 Ø3 4 4 0 1 5 16 3 5 16 2 5 16 Top Right Front Left Back 11 12 Siemens Building Technologies CC1N7451en HVAC Products 11 15 2004 ...

Страница 12: ...Dimensions QRA4 U Dimensions in inches 12 12 Siemens Building Technologies HVAC Products 11 15 2004 ...

Отзывы: