Assignment planning
3.6 Configuring the electrical structure
ET 200M
Operating Instructions, 12/2008, EWA-4NEB780600602-08
55
Filtering the 24 V DC supply
If, with a configuration with ungrounded reference potential, you supply the IM 153-x from a
battery, you must suppress the 24 V DC power supply. To do this, use a Siemens mains
filter, e.g. B84102-K40.
Insulation monitoring
If, on account of double faults, dangerous situations could occur, then you must provide
insulation monitoring.
3.6.4
Configuration of the ET 200M with isolated modules
Definition
With a configuration using isolated modules, the reference potentials are electrically isolated
from the control circuit (M
internal
) and load circuit (M
external
) (refer also to the following figure).
Application area
You use electrically isolated modules for:
●
all AC load circuits
●
DC load circuits with separate reference potential, e.g.
–
DC load circuits, the encoders for which have different reference potentials (e.g. if
grounded encoders are used far away from the controller and an equipotential
bonding isn´t possible)
–
DC power circuits, the positive poles (L +) of which are grounded (battery circuit).
Isolated modules and grounding concept
You can use isolated modules irrespective of whether the reference potential of the ET 200M
is grounded or not.
Содержание IM 153-4 PN
Страница 186: ...Functions 8 9 SNMP ET 200M 184 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 226: ...Interrupt error and system messages 9 2 PROFINET IO ET 200M 224 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 254: ...Order Numbers for the ET 200M ET 200M 252 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...
Страница 268: ...Glossary ET 200M 266 Operating Instructions 12 2008 EWA 4NEB780600602 08 ...