Communications
C.30 Writing parameters
HydroRanger 200 HMI
336
Operating Instructions, 06/2018, A5E36281317-AC
C.29.2
Parameter-specific index method
Set Parameter Index Location (4.11.) (Page 270)= Parameter-specific.
The Parameter-specific index method sets the index values for each parameter
independently. Use this method to read multiple parameters with different index values.
1.
Write the primary index, secondary index, and data format values into the appropriate
format register.
For example, send the integer value 01008 to register 46,921, in order to read the
following information:
–
Measured level [Level (3.2.8.3.)] (Page 256)
–
In units with three decimal places
–
From Transducer 1
2.
Read the value from the appropriate parameter register (the example uses 44,921).
Types of values are:
●
Numeric values (Page 339)
●
Bit values (Page 339)
●
Split values (Page 341)
●
Text messages (Page 342)
●
Relay function codes (2.8.1.4. Relay function only) (Page 343)
A value of 22,222 indicates that an error occurred. Specify a different format type and try
again.
C.30
Writing parameters
The method of writing parameters is similar to the method of reading them. Become familiar
with Reading parameters (Page 334) before attempting to write any.
To write parameter values to the device, follow these steps:
C.30.1
Global index method
Set Parameter Index Location (4.11.) (Page 270) = *Global.
1.
Write the primary index value into R43,999.
2.
Write the secondary index value into R43,998.
3.
Write the desired format value into the appropriate format register.
4.
Write the value to the appropriate parameter register.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......