Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
238
Operating Instructions, 06/2018, A5E36281317-AC
8.6.12.5
Convert reading (2.12.5.)
Multiplies the current value by the specified amount, to allow for scaling.
Index
Level
Values
Range: -999 ... 9999
Preset: 1.000
Related
Reading (3.2.8.2.) (Page 256)
Example:
●
If the measured value is in feet, enter 0.3333 to display the number of yards.
●
For simple linear volume conversions, set Units to 1 (meter) and then enter the volume
measurement per unit to get the correct conversion. For example, if the reservoir contains
100 liters per vertical meter, use 100 to get the reading in liters.
Note
•
This method does not calculate volume. It must not be used in place of the volume
parameters if any volume dependent features (such as pump efficiency) are used. To
calculate true volumes, see Volume (2.7.) (Page 185).
•
Avoid entering a value that exceeds the display capabilities when multiplied by the
maximum current reading. If value exceeds four digits, #### is shown.
8.6.12.6
Offset reading (2.12.6.)
Adds the specified value to the level reading, usually to reference the reading to sea level or
another data level.
Index
Level
Values
Range: -999 ... 9999
Preset: 0.000
Related
Reading (3.2.8.2.) (Page 256)
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......