Siemens HOTEL SOLUTION HTC3.1/A Скачать руководство пользователя страница 1

 

6

319

 

 

 

 

 

 

 

HOTEL SOLUTION™  

 

 

Room operator unit 

Room operator unit with 
built-in sensor 

HTC3.1/A

HTC3.1S/A

 

 

 

 

Room unit for operation of the individual room control system in hotel rooms 

 

Displays room temperature setpoint and setpoint adjustment 

 

Individual setpoint adjustment with "plus" and "minus" membrane switches 

 

Individual manual fan-speed selection for fan control (up to 3 speeds) 

 

Membrane switch for selection of "Auto" mode 

 

Room temperature detected with connected temperature sensor 

 

Room temperature detected with built-in temperature sensor (HTC3.1S/A) 

 
 

Application

 

The HTC3.1A and HTC3.1S/A room operator units are used in conjunction with a 
HRC3.. room controller. The room operator unit detects the temperature and trans-
mits it to the HRC3.. room controller for room temperature control.   
The room operator unit indicates the operating mode in the hotel room and can be 
used to operate the fan coil unit, either manually or automatically via the connected 
room controller.  

CM2N6319en 
31.07.2008 

Building Technologies

 

Содержание HOTEL SOLUTION HTC3.1/A

Страница 1: ...n of Auto mode Room temperature detected with connected temperature sensor Room temperature detected with built in temperature sensor HTC3 1S A Application The HTC3 1A and HTC3 1S A room operator units are used in conjunction with a HRC3 room controller The room operator unit detects the temperature and trans mits it to the HRC3 room controller for room temperature control The room operator unit i...

Страница 2: ... 1 A Room operator unit HTC3 1 SA Room operator unit with built in sensor Ordering When ordering please specify the quantity product name and type code 30 Room operator units HTC3 1 A Example Compatibility See assortment overview N6301 Mechanical design The room operator unit comprises Printed circuit board with the electronic circuit LCD display membrane switches for operation and terminal block ...

Страница 3: ...e fan speeds 1 2 and 3 manually Change from manual to automatic mode Auto Switching to Auto causes the fan speed to be set automatically by the controller Speed 1 2 or 3 The fan status is indicated by symbols across the bottom of the LCD display panel The temperature setpoint valid for the room is displayed in digits on the LCD display panel Throughout the period for which the guest is checked in ...

Страница 4: ...mperature sensor is disabled First room operator unit ID 1 MST 0 Master sensor enabled Second room operator unit ID 2 MST 1 Slave Third room operator unit ID 3 MST 1 Slave Fourth room operator unit ID 4 MST 1 Slave Fifth room operator unit ID 5 MST 1 Slave Further control loops can also be defined by means of a special application in the room controller In such cases other room operator units meas...

Страница 5: ...be mounted at eye level in the living area of the hotel room Lamps and other heat sources in the vicinity of the room temperature sensor must not be allowed to distort the measured temperature The room operator unit with the built in temperature sensor is not suitable for mounting within reach of the bed for example because items such as bedside lamps cause to0 great an increase in the measured te...

Страница 6: ...ed in EEPROM Environmental conditions Operating temperature 5 50 C Transport temperature 25 65 C Humidity 95 non condensing Air pressure during operation Min 700hPa 3000m above sea level Air pressure during transportation Min 700hPa 10 000m above sea level Standards Product safety Automatic electrical controls for household and similar use EN 60 730 1 and EN 60 730 2 11 Electromagnetic compatibili...

Страница 7: ... 6319A01 N1 6 1 2 3 4 B1 S2 Room operator unit type HTC3 1 A B1 Temperature sensor 10 kΩ NTC e g HSE1 1 HSE1 2 N1 HRC3 room controller Wiring diagram HTC3 1 A 1 2 5 S2 X12 6319A02 N1 6 1 2 3 4 3 4 S2 Room operator unit type HTC3 1S A N1 HRC3 room controller Wiring diagram HTC3 1S A STOP Caution Note the cross over between pins 3 and 4 7 8 Siemens HTC3 1 A HTC3 1S A Room operator units CM2N6319en B...

Страница 8: ...2 5 25 1 5 67 9 5 25 6319M01 Auto Dimensions in mm 3 108 140 5 80 5 6319M02 8 8 Siemens HTC3 1 A HTC3 1S A Room operator units CM2N6319en 2005 2008 Siemens Switzerland Ltd Subject to change Building Technologies 31 07 2008 ...