Maintenance and diagnostics 

 

4.2 Diagnostic events 

FST020 Function manual 
Function Manual, 09/2017, A5E42949526-AA 

133

 

Related 
The selected events will be shown in the display when they occur. Furthermore, they will be 

indicated on the output if Output (2), Input/output (3) and/or Input/output (4) is set to Status 

output and Status mode is set to Alarm item. 

 

Path 

Maintenance and diagnostics 

 Diagnostic events 

 Enable alarms 

 Process events (3) 

4.2.7.6

 

Process events (4) 

Description 
Various sensor alarms can be enabled to show in the display and on the output if they occur. 

 

Setting  Various process alarms selectable 
Default  - 

Related 
The selected events will be shown in the display when they occur. Furthermore, they will be 

indicated on the output if Output (2), Input/output (3) and/or Input/output (4) is set to Status 

output and Status mode is set to Alarm item. 

 

Path 

Maintenance and diagnostics 

 Diagnostic events 

 Enable alarms 

 Process events (4) 

4.2.7.7

 

Totalizer events 

Description 
Various sensor alarms can be enabled to show in the display and on the output if they occur. 

 

Setting  136 Totalizer 1 above alarm limit; 137 Totalizer 1 above warning limit; 138 Totalizer 1 be-

low warning limit; 139 Totalizer 1 below alarm limit 

Default   

Related 
The selected events will be shown in the display when they occur. Furthermore, they will be 

indicated on the output if Output (2), Input/output (3) and/or Input/output (4) is set to Status 

output and Status mode is set to Alarm item. 

 

Path 

Maintenance and diagnostics 

 Diagnostic events 

 Enable alarms 

 Totalizer events 

4.2.7.8

 

Device events 

Description 
If one of the selected events appears this affects the status icon, the related status output 

and the alarm on the communication interface. 

Содержание FST020

Страница 1: ...Function manual Answers for industry 09 2017 Edition Ultrasonic Flowmeters FST020 IP65 NEMA 4X SITRANS F ...

Страница 2: ......

Страница 3: ...RANS F Ultrasonic Flowmeters FST020 Function manual Function Manual 09 2017 A5E42949526 AA Introduction 1 Quick start 2 Setup 3 Maintenance and diagnostics 4 Communication 5 Security 6 Language 7 Support A ...

Страница 4: ...ay be operated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WAR...

Страница 5: ... 3 1 Sensor settings 19 3 1 1 Length unit 19 3 1 2 Length unit settings 19 3 1 3 Pipe settings 19 3 1 3 1 Pipe class 19 3 1 3 2 Pipe size 19 3 1 3 3 Outer pipe diameter 20 3 1 3 4 Wall thickness 20 3 1 3 5 Pipe material 20 3 1 3 6 Wall sound velocity 20 3 1 3 7 Liner settings 21 3 1 3 8 Inner pipe roughness 22 3 1 3 9 Inner pipe diameter 22 3 1 4 Upstream and downstream conditions 22 3 1 4 1 Distu...

Страница 6: ...User calibration 32 3 1 8 1 Slope 32 3 1 8 2 Path 1 offset 32 3 1 9 Multipoint calibration 33 3 1 9 1 Enable multipoint calibration 33 3 1 9 2 Asymmetric calibration table 33 3 1 9 3 Calibration point 34 3 1 9 4 Multipoint calibration table 34 3 1 10 Flow direction 35 3 1 11 Miscellaneous 35 3 1 11 1 Preamplifier Setting 35 3 1 11 2 Number of pulses to be transmitted 36 3 1 11 3 Minimum ringdown d...

Страница 7: ...ity 53 3 2 6 1 Units 53 3 2 6 2 Decimal places 53 3 2 6 3 Alarm and warning limits 53 3 2 7 Medium temperature 55 3 2 7 1 Units 55 3 2 7 2 Decimal places 55 3 2 7 3 Alarm and warning limits 55 3 3 Totalizers 57 3 3 1 Totalizer 1 57 3 3 1 1 Process value 57 3 3 1 2 Units 58 3 3 1 3 Custom units 58 3 3 1 4 Custom conversion factor 58 3 3 1 5 Decimal places 59 3 3 1 6 Direction 59 3 3 1 7 Fail safe b...

Страница 8: ...81 3 4 4 4 Pulse output 84 3 4 5 Channel 7 digital input 88 3 4 5 1 Input function 88 3 4 6 Channel 8 digital input 88 3 4 6 1 Input function 88 3 4 6 2 Input function settings 88 3 5 Date and time 88 3 5 1 Current date and time 88 3 5 2 Set date and time 89 3 6 Local display 89 3 6 1 FST020 Display 89 3 6 2 Brightness 90 3 6 3 Backlight 90 3 6 4 Contrast 90 3 7 Damping 91 3 7 1 Damping value 91 3...

Страница 9: ...th process value 103 3 10 9 6th process value 103 3 10 10 Trend scale mode 104 3 10 11 Trend log time window 104 3 10 12 Trend scale lower limit 104 3 10 13 Trend scale upper limit 105 3 11 View 4 105 3 11 1 Enable or disable 105 3 11 2 View 105 3 11 3 1st value 106 3 11 4 2nd value 106 3 11 5 3rd value 107 3 11 6 4th value 107 3 11 7 5th value 108 3 11 8 6th value 108 3 11 9 Trend scale mode 108 ...

Страница 10: ...ge 122 4 1 5 Location 122 4 1 6 Installation date 122 4 1 7 Manufacturer 122 4 1 8 Product name 123 4 1 9 Version read only 123 4 1 10 Order number read only 123 4 1 11 Serial number 123 4 1 12 FW version 124 4 1 13 HW version 124 4 1 14 Final assembly number 124 4 1 15 System type 125 4 1 16 Transmitter electronics 125 4 1 16 1 HW version 125 4 1 16 2 FW version 125 4 1 16 3 Serial number 125 4 1...

Страница 11: ...5 4 2 8 3 149 Transm temp below alarm limit 136 4 3 Maintenance 136 4 3 1 Copy configuration 136 4 3 2 Spare part replacement 136 4 3 2 1 Transmitter 136 4 3 2 2 Operating time 137 4 3 3 Electronic part identification 137 4 3 3 1 Transmitter cassette 137 4 3 3 2 Local display 139 4 3 3 3 I O cassette 140 4 3 3 4 Sensor cassette 140 4 4 Diagnostics 141 4 4 1 Sensor 141 4 4 1 1 Receiver signal 141 4...

Страница 12: ...minimum 155 4 5 4 6 Reset peak values 155 4 6 Characteristics 155 4 6 1 Transmitter 155 4 6 1 1 Design read only 155 4 7 SensorFlash 156 4 7 1 Eject 156 4 7 2 Installed read only 156 4 7 3 Capacity total read only 156 4 7 4 Capacity available read only 157 4 7 5 Data logging 157 4 7 5 1 Activation 157 4 7 5 2 Data logging mode 157 4 7 5 3 Logging interval 158 4 7 5 4 Process values 158 4 8 Simulat...

Страница 13: ...e 173 5 1 3 MSD connect write only 173 5 2 Modbus Channel 1 174 5 2 1 Slave address SW 174 5 2 2 Slave address HW read only 174 5 2 3 Baud rate 174 5 2 4 Parity framing 175 5 2 5 Floating point byte order 175 5 2 6 Integer byte order 175 5 2 7 Register mapping 176 5 2 7 1 Enable mapping 176 5 2 7 2 Source register 1 20 176 5 2 7 3 Target register 1 20 176 5 2 8 Modbus units 177 5 2 8 1 Mass flow u...

Страница 14: ...0 Function manual 12 Function Manual 09 2017 A5E42949526 AA 6 6 Deactivate user PIN 182 6 7 Auto logout 182 6 8 Auto logout 183 6 9 Logout 183 7 Language 185 7 1 Language 185 A Support 187 A 1 Technical support 187 Index 189 ...

Страница 15: ...re the relation if any between parameters is described As of chapter 3 Setup Page 19 the chapter and subchapter numbers equal the parameter numbers in the HMI structure For parameters with access level other than User for example Read only or Expert the access level is stated in parenthesis after the parameter name 1 3 Quick start wizards The device offers a set of wizards which will guide you thr...

Страница 16: ...dition are given in the following table Edition Note 09 2017 First edition 1 7 Device documentation package The user documentation package for this product includes the following documents Document Purpose Intended users Availability Application plan ning sheets Contains all information needed to plan the mechanical physical installation and control signals before the product ar rives Plant design...

Страница 17: ...echanical and electrical install ers instrument technicians Included in the delivery On documentation disk Available for download from homepage Functions Manual Contains descriptions of all functions that can be accessed via the local display HMI guide to setting parameters to obtain opti mum operation of the device Instrument tech nicians plant operators Available for download from homepage Hardc...

Страница 18: ...Introduction 1 7 Device documentation package FST020 Function manual 16 Function Manual 09 2017 A5E42949526 AA ...

Страница 19: ...ration path and sub wizards appropriate for your application 2 3 Sensor settings Description The sensor settings wizard will guide you through configuration of essential parameters 2 4 Process values The Process values wizard will guide you through setup of process values for your application The prioritizing of the process values automatically configures the measurement views on the display The p...

Страница 20: ...Quick start 2 6 Copy configuration FST020 Function manual 18 Function Manual 09 2017 A5E42949526 AA ...

Страница 21: ... Sensor settings Length units 3 1 3 Pipe settings 3 1 3 1 Pipe class Description Pipe class Read only Can only be changed via the Sensor Wizard Indicates the pipe class chosen from the pipe data library included in the sensor setup wizard 3 1 3 2 Pipe size Description Pipe size Read only Can only be changed via the Sensor Wizard Indicates the pipe class chosen from the pipe data library included i...

Страница 22: ...pe material Description Pipe material Read only Can only be changed via the Sensor Wizard Setting Read only Carbon steel Stainless steel ABS plastic Aluminum Black iron Brass Cast iron Copper nickel 70 30 Copper nickel 90 10 Copper Ductile iron FRP plastic Glass Hastelloy Inconel Kynar plastic Monel Nickel Polyethylene PVC plastic Teflon Titani um Default Can only be changed via the Sensor wizard ...

Страница 23: ... m Default 0 0 m Related Path Setup Sensor settings Pipe settings Liner settings Liner thickness 3 1 3 7 2 Liner material Description Liner material Read only Can only be changed via the Sensor Wizard Setting Read only Custom Cement Coal tar Enamel Glass Plastic Hi_dens_Poly PTFE Rub ber Default Custom Related Path Setup Sensor settings Pipe settings Liner settings Liner material 3 1 3 7 3 Liner s...

Страница 24: ... settings Pipe settings Inner pipe roughness 3 1 3 9 Inner pipe diameter Description Read only Calculated inner diameter of pipe clamp on Setting Default 0 0 m Related Path Setup Sensor settings Pipe settings Inner pipe diameter 3 1 4 Upstream and downstream conditions 3 1 4 1 Disturbed flow profile compensation Description Disturbed flow profile compensation enable disable Setting Enable Disabled...

Страница 25: ...tream flow disturbance The distance is given in pipe diameters Used for clamp on flow profile compensation Setting 0 to 40 Default 0 Related Path Setup Sensor settings Upstream and downstream conditions Upstream distance 3 1 4 4 Type of downstream condition Description Compensation for downstream pipe geometry Setting Straight run Single elbow Double elbow in plane Double elbow out of plane Reduce...

Страница 26: ...a the Sensor Wizard Indicates the fluid medium type chosen from the fluid data library included in the sensor setup wizard 3 1 5 2 Expected sound velocity Description Expected sound velocity in the medium at process temperature Setting 100 0 m s to 2500 0 m s Default 1500 0 m s Related Path Setup Sensor settings Fluid settings Expected sound velocity 3 1 5 3 Process temperature Description Tempera...

Страница 27: ...tion Input during setup Setting 0 0 kg m to 2000 0 kg m Default 1000 0 kg m Related Path Setup Sensor settings Medium characteristics Process density 3 1 6 Sensor selection 3 1 6 1 Sensor model Description Installed sensor model for multi path all must be the same Read only Can only be changed via the Sensor Wizard Indicates the Sensor model chosen from the sensor setup wizard Setting Read only FS...

Страница 28: ...etup Sensor settings Sensor selection Nominal sensor frequency 3 1 6 4 Sensor crystal projection Description Length of the crystal projection onto the emitting surface of the sensor clamp on Access level Expert user only Setting 0 0 m to 0 3 m Default 0 03409 m Related Path Setup Sensor settings Sensor settings Sensor crystal projection 3 1 6 5 Sensor phase velocity Description The velocity at whi...

Страница 29: ...or fixed time Description Fixed time in sensor wedge Access level Expert user only Setting 2 0 x 10 6 s to 200 0 x 10 6 s Default 10 61 x 10 6 s Related Path Setup Sensor settings Sensor settings Sensor fixed time 3 1 6 8 Mounting hole offset Description Distance between spacer hole and sensor front face Setting 0 0 m to 0 05 m Default 0 00953 m Related Path Setup Sensor settings Sensor settings M...

Страница 30: ...r selection Temperature code of the sensor 3 1 6 11 Temperature compensation factor Description Temperature compensation factors for the sensors Setting 0 0001 to 0 0009 Default 0 000638 Related Path Setup Sensor settings Sensor selection Temperature compensation factor 3 1 6 12 Length of sensor cables Description Length of sensor cable between transmitter DSL and any sensors All cables must have ...

Страница 31: ...ings Path settings Installed paths 3 1 7 2 Path 1 3 1 7 2 1 Sensor frequency Description Desired sensor frequency for path 1 Read only Setting 80000 0 Hz to 4000000 0 Hz Default Related Path Setup Sensor settings Path settings Path 1 Sensor frequency 3 1 7 2 2 Path geometry Description The number of crossings the signal makes through the pipe Reflect or Direct geometry for Path 1 For example Direc...

Страница 32: ...ath Setup Sensor settings Path settings Path 1 Sensor spacing 3 1 7 2 4 Zero point adjustment Description Zero point adjustment Can only be changed via the Sensor Wizard Note Important Please stop all flow in the pipe and perform this function The flow velocity is measured prior and after the function has been applied Setting 5 to 300 Default 10 Related Path Setup Sensor settings Path settings Pat...

Страница 33: ...Path Setup Sensor settings Path settings Path diagnostic alarm limits Percent bursts accepted alarm limit 3 1 7 3 2 Correlation factor alarm limit Description Sets the desired limit for the correlation factor If the measured correlation factor drops below this limit for any installed path an alarm will be issued Setting Min 0 0 Max 1 0 Default 0 95 Related Path Setup Sensor settings Path settings ...

Страница 34: ...Min 0 0 dB Max 100 dB Default 20 dB Related Path Setup Sensor settings Path settings Path diagnostic alarm limits SNR alarm limit 3 1 8 User calibration 3 1 8 1 Slope Description A single point flow correction applied to volume flow equally at any flow rate Q Q Slope e g Slope of 0 99 1 correction Setting 0 5 to 2 0 Default 1 0 Related Path Setup Sensor settings User calibration Slope 3 1 8 2 Path...

Страница 35: ...table Description Note Access level Expert user only Only available for LUILOCAL_CURRENT_LUI_ACCESS_LEVEL SUP AND PID_ProtectCalibrationTable 0 AND PID_EnableUserCalibrationTable 1 Usage of the calibration table Unidirectional All 20 calibration points are used for positive flow calibration and are then mirrored for negative flow Bidirectional The first 10 calibration points are used for positive ...

Страница 36: ...ts 1 through 20 for unidirectional flow or calibration points 1 through 20 for bidirectional positive flow If 0 0 the calibration point is not used Access level Expert user only Note Only available for PID_ProtectCalibrationTable 1 OR PID_EnableUserCalibrationTable 1 Setting 0 0 m3 s to 100000 0 m3 s Default 0 0 m3 s Related Path Setup Sensor settings Multipoint calibration Multipoint calibration ...

Страница 37: ...n Default positive flow direction is indicated by the arrow on the sensor Setting Negative Positive Default Positive Related Path Setup Sensor settings Flow direction 3 1 11 Miscellaneous 3 1 11 1 Preamplifier Setting Description Preamplifier settings Access level Expert user only Auto default Will automatically turn on the pre amplifier if the sensor type is clamp on Off Turns off the pre amplifi...

Страница 38: ...10 Default 5 Related Path Setup Sensor settings Miscellaneous Number of pulses to be transmitted 3 1 11 3 Minimum ringdown delay Description The minimum ringdown delay is needed for optimized signal processing Access level Expert user only Read only The minimum ringdown delay setting for optimized signal processing is 2000 000122 μs 3 1 11 4 Electronic time delay Description The time delay induced...

Страница 39: ...onfiguration data is needed Back up and record data as necessary The wizard configures the device for use with the Siemens sensor test blocks including sensor size and sensor path It also allows for saving the setting 3 1 12 2 Sensor size Sensor size Sensor path A1 Path 1 Path 2 A2 Path 1 Path 2 B1 Path 1 Path 2 B2 Path 1 Path 2 B3 Path 1 Path 2 C1 Path 1 Path 2 C2 Path 1 Path 2 C3 Path 1 Path 2 D...

Страница 40: ... d 1 barrel 31 US gallons BBL42 s 1 barrel 42 US gallons BBL42 min 1 barrel 42 US gallons BBL42 h 1 barrel 42 US gallons BBL42 d 1 barrel 42 US gallons KBBL42 d Thousand barrels per day MBBL42 d million barrels per day BBL31 5 s 1 barrel 31 5 US gallons BBL31 5 min 1 barrel 31 5 US gallons BBL31 5 h 1 barrel 31 5 US gallons BBL31 5 d 1 barrel 31 5 US gallons ft s cubic feet per second ft min cubic...

Страница 41: ...ription Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Standard volume flow Decimal places 3 2 1 5 Low flow cut off Description Volume flow limit for low flow cut off Below limit v...

Страница 42: ... limit 3 2 1 6 2 Upper warning limit Description Exceeding this limit causes a warning Setting 896 40 m3 h to 896 40 m3 h Default 896 40 m3 h Related Path Setup Process values Volume flow Alarm and warning limits Upper warning limit 3 2 1 6 3 Lower warning limit Description Falling below this limit causes a warning Setting 896 40 m3 h to 896 40 m3 h Default 896 40 m3 h Related Path Setup Process v...

Страница 43: ... 2 2 Mass flow 3 2 2 1 Units Description Select units for displayed mass flow rate Units are not applied at communication interface Setting g s grams per second g min grams per min g h grams per hour kg s kilograms per second kg min kilograms per minute kg h kilograms per hour kg d kilograms per day t min 1 t 1000 kg t h 1 t 1000 kg t d 1 t 1000 kg STon min 1 STon 2000 lb STon h 1 STon 2000 lb STo...

Страница 44: ...Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Mass flow Decimal places 3 2 2 5 Low flow cut off Description Mass flow limit for low flow cut off Below limit mass flow ...

Страница 45: ...r warning limit Description Exceeding this limit causes a warning Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h Related Path Setup Process values Mass flow Alarm and warning limits Upper warning limit 3 2 2 6 3 Lower warning limit Description If the mass flow value falls below this limit a warning is triggered Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h ...

Страница 46: ...h Related Path Setup Process values Mass flow Alarm and warning limits Hysteresis 3 2 3 Flow velocity 3 2 3 1 Units Description Select units for displayed flow velocity Units are not applied at communication interface Units for flow velocity values Setting m s meters per second m h meters per hour in s inches per second in min inches per minute ft s feet per second ft min feet per minute custom un...

Страница 47: ...conversion factor 3 2 3 4 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Flow velocity Decimal places 3 2 3 5 Low flow cut off Description Flow velocity ...

Страница 48: ...limits Description If process value exceeds this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Flow velocity Alarm and warning limits Upper warning limit 3 2 3 6 3 Lower warning limit Description If process value falls below this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 ...

Страница 49: ...rning limits Hysteresis Setting 0 m s to 9999997952 m s Default 0 00 m s Related Path Setup Process values Flow velocity Alarm and warning limits Hysteresis 3 2 4 Sound velocity 3 2 4 1 Units Description Select units for displayed sound velocity Units are not applied at communication interface Setting m s meters per second m h meters per hour in s inches per second in min inches per minute ft s fe...

Страница 50: ...t sound velocity values based on SI velocity units m s Setting Default 1 0 Related Path Setup Process values Sound velocity Custom conversion factor 3 2 4 4 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default ...

Страница 51: ...ed Path Setup Process values Sound velocity Alarm and warning limits Upper warning limit 3 2 4 5 3 Lower warning limit Description if the process value falls below this limit a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Sound velocity Alarm and warning limits Lower warning limit 3 2 4 5 4 Lower alarm limit Description If t...

Страница 52: ...cation interface Read only Setting μg l micrograms per liter μg m micrograms per cubic meter mg l milligrams per liter g ml grams per milliliter g cm grams per cubic centimeters g l grams per liter kg l kilograms per liter kg m kilograms per cubic meter lb in pounds per cubic inch lb gal pounds per US gallon lb ft pounds per cubic foot STon yd 1 STon 2000 lb custom units see Custom units Custom co...

Страница 53: ...e local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Density Decimal places 3 2 5 5 Alarm warning limits 3 2 5 5 1 Upper alarm limit Description If density value exceeds this limit an alarm is triggered Setting 0 00 kg m to 10000 00 kg m Default 9...

Страница 54: ...s values Density Alarm and warning limits Lower warning limit 3 2 5 5 4 Lower alarm limit Description If density value falls below this limit an alarm is triggered Setting 0 00 kg m to 10000 00 kg m Default 1 00 kg m Related Path Setup Process values Density Alarm and warning limits Lower alarm limit 3 2 5 5 5 Hysteresis Description Sets the hysteresis for alarm and warning limits The hysteresis i...

Страница 55: ...ets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 decimal places Related Path Setup Process values Kinematic viscosity Decimal places 3 2 6 3 Alarm and warning limits 3 2 6 3 1 Upper alarm limit Description If process value exceeds t...

Страница 56: ...it a warning is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Kinematic viscosity Alarm and warning limits Lower warning limit 3 2 6 3 4 Lower alarm limit Description If process value falls below this limit an alarm is triggered Setting 9999997952 m s to 9999997952 m s Default 9999997952 m s Related Path Setup Process values Kinematic v...

Страница 57: ...s Celsius F degrees Fahrenheit R degrees Rankine K kelvins Default C degrees Celsius Related Path Setup Process values Medium temperature Units 3 2 7 2 Decimal places Description Sets the decimal places for the process value displayed in the local display Setting Auto No decimal place 1 decimal place 2 decimal places 3 decimal places 4 decimal places 5 decimal places 6 decimal places Default 2 dec...

Страница 58: ...s limit causes a warning Related Setting 272 77 to 400 00 C Default 270 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Upper warn ing limit 3 2 7 3 3 Lower warning limit Description Falling below this limit causes a warning Setting 272 77 00 to 400 00 C Default 270 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Lower warn ing ...

Страница 59: ...eresis for alarm and warning limits The hysteresis is the distance between the limits for activation and deactivation of an alarm warning Setting 0 00 C to 200 00 C Default 0 00 C Related Path Setup Process values Medium temperature Alarm and warning limits Hysteresis 3 3 Totalizers 3 3 1 Totalizer 1 3 3 1 1 Process value Description Select the process value to be totalized Setting Mass flow Volum...

Страница 60: ...allons BBL42 1 barrel 42 US gallons in cubic inches ft cubic feet yd cubic yards bush bushels Process value Standard volume flow Nl normal liters Nm normal cubic meters Sl standard liters Sft standard cubic feet Sm standard cubic meters custom units see Custom units Custom conversion factor Default kg kilograms Related Path Setup Totalizers Totalizer 1 Units 3 3 1 3 Custom units Description User s...

Страница 61: ... Description Totalizer 1 direction Setting Forward and backward Forward Backward Hold Default Forward Related Path Setup Totalizers Totalizer 1 Direction 3 3 1 7 Fail safe behaviour Description Behaviour of the totalizer during the occurrence of bad input value Setting RUN totalization is continued using the bad input value HOLD totalization is stopped MEMORY totalization is continued based on the...

Страница 62: ...7952 m to 9999997952 m Setting Cancel OK Default Cancel Related Path Setup Totalizers Totalizer 1 Preset 3 3 1 10 Alarm and warning limits 3 3 1 10 1 Upper alarm limit Description Alarm is triggered if Totalizer 1 value is above the limit Setting Process value Mass flow 9999997952 kg to 9999997952 kg Process value Volume flow 9999997952 m to 9999997952 m Default Process value Mass flow 9999997952 ...

Страница 63: ... 9999997952 m to 9999997952 m Default Process value Mass flow 9999997952 kg Process value Volume flow 9999997952 m Related Path Setup Totalizers Totalizer 1 Alarm and warning limits Lower warning limit 3 3 1 10 4 Lower alarm limit Description Alarm is triggered if Totalizer 1 value is below the limit Setting Process value Mass flow 9999997952 kg to 9999997952 kg Process value Volume flow 999999795...

Страница 64: ...f input and output is described in the following table Table 3 1 Hardware and software configuration of the input output channels Channel HW configuration fixed when ordering SW configuration available to the user 1 Modbus Modbus 2 Signal output Outputs Current output 0 4 20 mA 3 Relay output Status Output Alarm class Alarm item NAMUR status signals 4 Signal input output Outputs Frequency ouput Pu...

Страница 65: ...lt current value Recommended setting range for lower fault current Recommended setting range for upper fault current Measuring range Figure 3 1 Current limits for NAMUR configuration The fail safe current output signal can be selected to Lower fault current defined in the Loop current scale selection Upper fault current defined in the Loop current scale selection Last valid value the last process ...

Страница 66: ...cut off Upper range value Maximum output current Upper fault current Lower range value Lower saturation limit Span Current output setting Process value Mass flow Direction Positive Loop current scale 4 20 mA maximum 25 mA Upper range value 100 kg h Lower range value 400 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h ...

Страница 67: ...ower range value Low flow cut off Upper range value Upper saturation limit Lower saturation limit Lower fault current Span Current output setting Process value Mass flow Direction Bidirectional Loop current scale 4 20 mA NAMUR Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h ...

Страница 68: ...ling Lower range value Low flow cut off Upper range value Upper saturation limit Lower saturation limit Lower fault current Span Current output setting Process value Mass flow Direction Bidirectional Loop current scale 4 20 mA US Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Minimum current Low flow cut off 25 kg h ...

Страница 69: ... Process value Mass flow Direction Bidirectional Symmetric Loop current scale 4 20 mA NAMUR Upper range value 400 kg h Lower range value 100 kg h Fail safe behaviour Upper fault current Low flow cut off 25 kg h Pulse output The pulse output function supplies pulses equivalent to a configured amount of accumulated volume or mass The pulse width is configured and the pulse repetition is proportional...

Страница 70: ...ms Note Pulse width must be selected with the view that remaining time is always greater than pulse width at the highest measured flow Frequency output The frequency output function supplies a frequency 50 duty cycle proportional to the selected process value Frequency is calculated as follows Example This example shows how to calculate the output frequency for any measured flowrate Frequency outp...

Страница 71: ...ess value to 0 A warning will occur in case of negative flow This warning can be output on the status output if Status mode is set to Alarm item and the Process alarms 1 relevant process value below warning limit is selected 3 4 1 Alarm status Depending on the Status mode setting multiple alarms can be signaled on the output and selected from the alarm class or the alarm item lists Alarm class Ala...

Страница 72: ...n the input is inactive Note Changing polarity Changing the polarity triggers the signal input to execute the set functionality 3 4 2 Channel 2 output 3 4 2 1 Operation mode Description Operation mode Sets the output functionality for channel operation Setting Off Current output Default Off Related Path Setup Inputs and outputs Channel 2 output Operation mode 3 4 2 2 Active operation read only Des...

Страница 73: ...3 4 2 4 Current output 3 4 3 4 1 Process value Description Select process value for the current output Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default Mass flow Related Path Setup Inputs and outputs Channel 2 output Current output Process value 3 4 3 4 2 Direction Description Flow direction filter applicable for process values mass...

Страница 74: ...NAMUR Related Path Setup Inputs and outputs Channel 2 output Current output Loop current scale 3 4 3 4 4 Upper range value Description Sets value at 100 of measuring span and corresponds to a loop current of 20 mA Setting and Default are sensor specific depending on the setting in Process value and depending on the Units setting Setting 3682800 00 kg h to 3682800 00 kg h Default 3682800 00 kg h Re...

Страница 75: ...requirements of signal stability and response time Setting 0 00 s to 100 00 s Default 0 00 s Related Path Setup Inputs and outputs Channel 2 output Current output Damping value 3 4 3 4 7 Fail safe behaviour Description Current output reaction in case of a fault Setting Lower fault current Upper fault current Last valid value Current value Fail safe value Default Lower fault current Related Path Se...

Страница 76: ...ff delay Description Set the time delay between resetting alarm condition and de activating the output Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 2 output Status output Off delay 3 4 3 Channel 3 relay 3 4 3 1 Operation mode Description Select the operation mode for the relay output Setting Alarm class Alarm item Default Alarm class Related Path Setup Input...

Страница 77: ...07 Flow measurement 08 DSL internal 14 Path 1 No signal 26 Sensor temp comp 28 Default None Related Path Setup Inputs and outputs Channel 3 relay Sensor alarms 1 3 4 3 4 Sensor alarms 2 Description Selection of alarm items that impact the output Mainly sensor alarms Applicable if Status mode Alarm item Setting 34 Invalid flow meas 36 Configuration 2 37 DSL system monitor Default None Related Path ...

Страница 78: ...ion of alarm items that impact the output Applicable if Status mode Alarm item For hydrocarbon and gas applications only Setting 228 Sound velocity above alarm limit 229 Sound velocity above warning limit 230 Sound velocity below warning limit 231 Sound velocity below alarm limit 232 Flow velocity above alarm limit 233 Flow velocity above warning limit 234 Flow velocity below warning limit 235 Flo...

Страница 79: ...uts Channel 3 relay Totalizer alarms 3 4 3 9 Device alarms Description Device alarms If one of the selected events appears this affects the status icon the related status output and the alarm on the communication interface Setting 148 Transm temp above alarm limit 149 Transm temp below alarm limit 150 Sensor signal disrupted 159 Internal error in transmitter Default None Related Path Setup Inputs ...

Страница 80: ...s Channel 3 relay Input output alarms 3 4 3 11 Simulation alarms 1 Description Selection of alarm items that impact the output Mainly simulation alarms Applicable if Status mode Alarm item Setting 160 Mass flow simulated 161 Volume flow simulated 162 Density simulated 163 Medium temp simulated 167 Totalizer 1 simulated Default None Related Path Setup Inputs and outputs Channel 3 relay Simulation a...

Страница 81: ...arm Process value warning Mainte nance demanded Maintenance required None Default Related Path Setup Inputs and outputs Channel 3 relay Alarm class 3 4 3 14 NAMUR status signal Description Selection of NAMUR status signals which impact the status output Each diagnostic event is allocated to a NAMUR status signal Application if Status mode Alarm class and Status icons NAMUR Setting Failure Function...

Страница 82: ...3 4 3 17 Off delay Description Set the time delay between resetting alarm condition and de activating the output Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 3 relay Off delay 3 4 4 Channel 4 input output 3 4 4 1 Operation mode Description Shows the configured Operation mode Use Change operation mode to set the mode Read only Setting Off Frequency output Pul...

Страница 83: ...quency output Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default Volume flow Related Path Setup Inputs and outputs Channel 4 input output 4 Frequency output Process value 3 4 3 3 2 Direction Description Flow direction filter applicable for process values mass flow volume flow flow velocity standard volume flow rate only hydrocarbon an...

Страница 84: ... 0 Hz to 12500 0 Hz Default 0 0 Hz Related Path Setup Inputs and outputs Channel 4 input output Frequency output Frequency value low 3 4 3 3 5 Upper range value Description Sets value at 100 of measuring span and corresponds to Frequency value high Setting and Default are sensor specific depending on the setting in Process value and depending on the Units setting Setting 10800000000 00 kg h to 108...

Страница 85: ...e constant of damping filter for frequency output signal Setting 0 0 s to 100 0 s Default 0 0 s Related Path Setup Inputs and outputs Channel 4 input output Frequency output Damping value 3 4 3 3 8 Fail safe behaviour Description Frequency output reaction in case of a fault Setting Minimum frequency Maximum frequency Last valid value Current valid fail safe value Default Last valid value Related P...

Страница 86: ... 0 0 Hz Related Path Setup Inputs and outputs Channel 4 input output Frequency output Fail safe value 3 4 4 4 Pulse output 3 4 3 4 1 Process value Description Select process value for the pulse output Setting Mass flow Volume flow Default Volume flow Related Path Setup Inputs and outputs Channel 4 input output Pulse output Process value 3 4 3 4 2 Direction Description Flow direction filter Setting...

Страница 87: ...0 lb T 1 T 2240 lb oz ounces lb pounds custom units see Custom units Custom conversion factor Default I liters Related Path Setup Inputs and outputs Channel 4 input output Pulse output Pulse units 3 4 3 4 4 Custom units Description User specific string to define custom pulse units Setting Default Related Path Setup Inputs and outputs Channel 4 input output Pulse output Custom units 3 4 3 4 5 Custo...

Страница 88: ... 1 Related Path Setup Inputs and outputs Channel 4 input output Pulse output Pulses per amount 3 4 3 4 8 Pulse width units Description Units of pulse duration value used to configure Ch4 pulse width Setting s seconds ms milliseconds μs micro seconds Default s seconds Related Path Setup Inputs outputs Channel 4 input output Pulse output Pulse width units 3 4 3 4 9 Polarity Description Logical polar...

Страница 89: ...output Fail safe behav iour 3 4 3 4 11 Fail safe value Description Output value in case of a fault and when fail safe behaviour configured to Fail safe value Setting 0 0 pulses s to 12500 0 pulses s Default 1 0 pulses s Related Path Setup Inputs and outputs Channel 4 input output Pulse output Fail safe value 3 4 3 4 12 Fail safe minimum time Description Minimum time the output stays in fail safe m...

Страница 90: ...d Path Setup Inputs and outputs Channel 7 digital input Input function 3 4 6 Channel 8 digital input 3 4 6 1 Input function Description Shows the digital input function Selects the signal input functionality 3 4 6 2 Input function settings Setting Off Start Stop totalizer 1 on level Default Off Related Path Setup Inputs and outputs Channel 8 digital input Input function 3 5 Date and time 3 5 1 Cur...

Страница 91: ... all timestamps of logged information Setting Default Related Path Setup Date and time Set date and time 3 6 Local display 3 6 1 FST020 Display The system can be configured to show up to six different views In view 1 only measurement or diagnostic views can be selected In views 2 to 6 all view types can be selected Measurement views Single value Three values 1 value and bargraph 1 value and graph ...

Страница 92: ...0 50 60 70 80 90 100 Default 50 Related Path Setup Local display Brightness 3 6 3 Backlight Description Select between always on or backlight switch off after 10 minutes Setting Automatic Always on Default Automatic 30 s Related Path Setup Local display Backlight 3 6 4 Contrast Description Adjust contrast to improve local display conditions Setting 0 10 20 30 40 50 60 70 80 90 100 Default 80 Relat...

Страница 93: ...vailable process values for the meter Setting Volume flow Mass flow Totalizer 1 Sound velocity Flow velocity Pressure Kinematic viscosity Density Medium temperature Default Related Path Setup Local display Damping Process values 1 3 7 3 Process values 2 Description Available process values for the meter Setting API gravity Standard API gravity Specific gravity Standard specific gravity Rate of cha...

Страница 94: ...s value must be configured If 1 value and graph is selected 1st process value Trend scale mode and Trend log time window must be configured If Six values or Six diagnostic values is selected 1st process value 2nd process value 3rd process value 4th process value 5th process value and 6th process value must be configured Path Setup Local display View 1 View 3 8 2 1st value Description The display 1...

Страница 95: ...ault Density Related This parameter is only available if View 1 is set to Three values Six values or Six diagnostic values Path Setup Local display View 1 2nd value 3 8 5 3rd value Description The display 3rd process value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Totalizer 2 Totalizer 3 Pressure Medium temperature Default M...

Страница 96: ...lay 5th process value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Process viscosity Fluid temperature Totalizer 1 Default Process pressure Related This parameter is only available if View 1 is set to Six values or Six diagnostic values Path Setup Local display View 1 5th process value 3 8 8 6th process value Description The display 6th process value can be se...

Страница 97: ...cale mode 3 8 10 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 minute 5 minutes 15 minutes 30 minutes 1 hour 2 hours 3 hours Default 5 minutes Related This parameter is only available if View is set to 1 value and graph Path Setup Local display View 1 Trend log time window 3 8 11 Trend scale lower limit Description The Trend s...

Страница 98: ...to Fixed Path Setup Local display View 1 Trend scale upper limit 3 9 View 2 3 9 1 Enable or disable Description In this parameter View 2 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is selected all parameters for View 2 must be configured Path Setup Local display View 2 Enable or disable 3 9 2 View Description The display View 2 can be configured Setting Single value ...

Страница 99: ...3rd process value 4th process value 5th process value and 6th process value must be configured Path Setup Local display View 2 View 3 9 3 1st value Description The display 1st Process Value can be selected This process value is shown in all view types Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Volume flow Related P...

Страница 100: ...n The display 4th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Volumeflow Related This parameter is only available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 2 4th Process Value 3 9 7 5th process value Description The display 5th Process Value can be selected Setting Mass flow Volume flow Density Fluid ...

Страница 101: ... be selected with automatic scaling or fixed scaling Setting Auto Fixed Default Auto Related This parameter is only available if View is set to Totalizer or 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be configured Path Setup Display View 2 Trend Scale Mode 3 9 10 Trend log time window Description The Trend log time window logging period time axi...

Страница 102: ...ode is set to Fixed Path Setup Display View 2 Trend Scale Lower Limit 3 9 12 Trend scale upper limit Description The Trend Scale Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 2 Trend Scale Upper Limit 3 10 View 3 3 10 1 Enable or ...

Страница 103: ...ess value and 3rd process value must be configured If Totalizer or 1 value and graph is selected 1st process value Trend scale mode and Trend log time window must be configured If 1 value and bargraph is selected 1st process value must be configured If Six values or Six diagnostic values is selected 1st process value 2nd process value 3rd process value 4th process value 5th process value and 6th p...

Страница 104: ...scosity Total izer 1 Medium Temperature Default Flow velocity Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 2 2nd Process Value 3 10 6 3rd process value Description The display 3rd Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Med...

Страница 105: ...rocess value Description The display 5th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Totalizer 1 Related This parameter is only available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 3 5th Process Value 3 10 9 6th process value Description The display 6th Process Value can be selected Setting Mass flow V...

Страница 106: ...nd Scale Mode 3 10 11 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 Minute 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only available if View is set to Totalizer or 1 Value and Graph Path Setup Display View 3 Trend log time window 3 10 12 Trend scale lower limit Descriptio...

Страница 107: ... to Fixed Path Setup Display View 3 Trend Scale Upper Limit 3 11 View 4 3 11 1 Enable or disable Description In this parameter View 4 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is selected all parameters for View 4 must be configured Path Setup Display View 4 Enable or disable 3 11 2 View Description The display View 4 can be configured Setting Single value Three va...

Страница 108: ...nternal temperature Ch3 value Ch4 value Reynolds number RxGain up path 1 RxGain down path 1 SNR up path 1 SNR down path 1 Sound velocity path 1 Flow velocity path 1 Delta time path 1 Travel time up path 1 Travel time down path 1 Correla tion factor path 1 Percentage of bursts accepted path1 Peak amplitude up path 1 Peak amplitude down path 1 Min acc travel time path 1 Min acc travel time path 1 Ma...

Страница 109: ...c travel time path 1 Max acc travel time path 1 Default Sound velocity path 1 Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 4 3rd Value 3 11 6 4th value Description The display 4th Process Value can be selected Setting Transmitter internal temperature Reynolds number RxGain up path 1 RxGain down path 1 SNR up pat...

Страница 110: ... Six Values or Six Diagnostic Values Path Setup Display View 4 5th value 3 11 8 6th value Description The display 6th Process Value can be selected Setting Transmitter internal temperature Reynolds number RxGain up path 1 RxGain down path 1 SNR up path 1 SNR down path 1 Sound velocity path 1 Flow velocity path 1 Delta time path 1 Travel time up path 1 Travel time down path 1 Correlation factor pat...

Страница 111: ...te 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only available if View is set to Totalizer or 1 Value and Graph Path Setup Display View 4 Trend log time window 3 11 11 Trend scale lower limit Description The Trend Scale Lower Limit defines the scaling lower limit of the value axis for the fixed mode Setting Default 0 Related This parameter is o...

Страница 112: ...ble 3 12 2 View Description The display View 5 can be configured Setting Single value Three values Totalizer Dosing 1 value and bargraph 1 value and graph Six values Six diagnostic values Alarm list Default Three values Related If Single Value or Dosing is selected 1st Process Value must be configured If Three Values is selected 1st Process Value 2nd Process Value and 3rd Process Value must be con...

Страница 113: ...mperature Default Totalizer 1 Related Path Setup Display View 5 1st value 3 12 4 2nd value Description The display 2nd Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Density Related This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Set...

Страница 114: ...available if View is set to Six Values or Six Diagnostic Values Path Setup Display View 5 4th Process Value 3 12 7 5th process value Description The display 5th Process Value can be selected Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Total izer 1 Medium temperature Default Totalizer 1 Related This parameter is only available if View is set to Six Values ...

Страница 115: ...r 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be configured Path Setup Display View 5 Trend Scale Mode 3 12 10 Trend log time window Description The Trend log time window logging period time axis length can be selected Setting 1 Minute 5 Minutes 15 Minutes 30 Minutes 1 Hour 2 Hours 3 Hours Default 5 Minutes Related This parameter is only availabl...

Страница 116: ...Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 5 Trend Scale Upper Limit 3 13 View 6 3 13 1 Enable or disable Description In this parameter View 6 can be enabled Setting Disabled Enabled Default Enabled Related If Enabled is select...

Страница 117: ...and Trend log time window must be configured If 1 Value and Bargraph is selected 1st Process Value must be configured If Six Values or Six Diagnostic Values is selected 1st Process Value 2nd Process Value 3rd Process Value 4th Process Value 5th Process Value and 6th Process Value must be configured Path Setup Local display View 6 View 3 13 3 1st process value Description The display 1st Process Va...

Страница 118: ...This parameter is only available if View is set to Three Values Six Values or Six Diagnostic Values Path Setup Display View 6 3rd Process Value 3 13 6 4th process value Description The display 4th Process Value can be selected Setting Mass flow Volume flow Density Fluid Temperature Totalizer 1 Default Volumeflow Related This parameter is only available if View is set to Six Values or Six Diagnosti...

Страница 119: ...Six Values or Six Diagnostic Values Path Setup Display View 6 6th Process Value 3 13 9 Trend scale mode Description The Trend Scale Mode can be selected with automatic scaling or fixed scaling Setting Auto Fixed Default Auto Related This parameter is only available if View is set to Totalizer or 1 Value and Graph If Fixed is selected Trend Scale Lower Limit and Trend Scale Upper Limit must be conf...

Страница 120: ...etting Default 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path Setup Display View 6 Trend Scale Lower Limit 3 13 12 Trend scale upper limit Description The Trend Scale Upper Limit defines the scaling upper limit of the value axis for the fixed mode Setting options Default setting 0 Related This parameter is only available if Trend Scale Mode is set to Fixed Path...

Страница 121: ...Setup 3 14 Status icons FST020 Function manual Function Manual 09 2017 A5E42949526 AA 119 Related Path Setup Local display Status icons ...

Страница 122: ...Setup 3 14 Status icons FST020 Function manual 120 Function Manual 09 2017 A5E42949526 AA ...

Страница 123: ...nance and diagnostics Identification Long tag 4 1 2 Tag Sets a unique short tag name for device or measurement point Limited to 8 characters Setting User configurable Default characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance diagnostics Identification Tag 4 1 3 Descriptor Sets unique description for device Limited to 32 characters Setting User configurable Default 16 characters A B C X Y...

Страница 124: ...nique location for device Limited to 32 characters Setting User configurable Default 32 characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance and diagnostics Identification Location 4 1 6 Installation date Sets the installation date of the device Setting User configurable Default 16 characters A B C X Y Z 1 2 3 7 8 9 Related Path Maintenance and diagnostics Identification Installation date 4...

Страница 125: ...oduct Version according to order can be viewed Setting Default WM int DSL Related Path Maintenance and diagnostics Identification Version 4 1 10 Order number read only Description System order number MLFB can be viewed The system order number consists of three parts Also shown on the device nameplate Setting Default Related Path Maintenance and diagnostics Identification System order number 4 1 11...

Страница 126: ...evice Setting Default Related Path Maintenance and diagnostics Identification FW version 4 1 13 HW version Displays version number corresponding to electronics hardware of device Setting Default Related Path Maintenance and diagnostics Identification HW version 4 1 14 Final assembly number Displays number corresponding to materials and components used in final assembly of device Setting 0 to 42949...

Страница 127: ...er electronics 4 1 16 1 HW version Displays version number corresponding to electronics hardware of device Setting Default Related Path Maintenance and diagnostics Identification HW version 4 1 16 2 FW version Displays version number corresponding to software or firmware embedded in device Setting Default Related Path Maintenance and diagnostics Identification FW version 4 1 16 3 Serial number Des...

Страница 128: ...Maintenance and diagnostics Identification Transmitter Order number 4 1 16 5 Comm interface serial number Description Communication interface serial number Setting Default Related Path Maintenance and diagnostics Identification Transmitter Comm interface serial num ber 4 1 17 Local display Description Local display Setting HW version 1 01 00 Default Setting FW version 1 04 13 09 Default Setting HM...

Страница 129: ...Description Displays DSL versions Setting FW version Default Related Path Maintenance and diagnostics Identification DSL 4 1 20 Sensor 4 1 20 1 Type read only Description The name of the digital sensor Path Maintenance and diagnostics Identification Sensor Type 4 1 20 2 Sensor type read only Description Identification of the sensor type Used by the transmitter to enable technology specific functio...

Страница 130: ...er 4 1 20 4 Sensor type read only Description Type of sensor Setting SITRANS FSS200 Clamp on SITRANS FSS600 Clamp on Default Related Path Maintenance and diagnostics Identification Sensor Sensor type 4 1 20 5 Sensor firmware version read only Description Sensor firmware version Setting Default Related Path Maintenance and diagnostics Identification Sensor Sensor firmware version 4 1 20 6 Frontend ...

Страница 131: ...list of logged events Path Maintenance and diagnostics Diagnostic events Diagnostic log 4 2 3 Clear diagnostic log Description The diagnostic log can be reset using this parameter Setting Cancel OK Default Cancel Related When you confirm the reset by selecting OK the Diagnostic log will be cleared Path Maintenance and diagnostics Diagnostic events Clear diagnostic log 4 2 4 Acknowledge mode Descri...

Страница 132: ... DE11 Failed to read FATAL_ERROR_PAGE from DE12 Failed to read SHUT_DOWN_PAGE from DE21 The EEPROM data is inconsistent DE22 Inconsistency of totalizer 1 values DE26 parameter cache full DE27 Unsupported sensor units De28 Communications module not found DE29 Incomplete sensor connected DE30 Invalid sensor type Default Communication module not found Path Maintenance and diagnostics Diagnostic event...

Страница 133: ... they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Sensor events 1 4 2 7 2 Sensor events 2 Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting 34 Invalid flow meas 36 Configurati...

Страница 134: ...cess events 1 4 2 7 4 Process events 2 Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting Various process alarms selectable Default Related The selected events will be shown in the display when they occur Furthermore they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status m...

Страница 135: ...ut output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Process events 4 4 2 7 7 Totalizer events Description Various sensor alarms can be enabled to show in the display and on the output if they occur Setting 136 Totalizer 1 above alarm limit 137 Totalizer 1 above warning limit 138 Totalizer 1 ...

Страница 136: ...vents will be shown in the display when they occur Furthermore they will be indicated on the output if Output 2 Input output 3 and or Input output 4 is set to Status output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Simulation events 1 4 2 7 10 Simulation events 2 Description Various sensor alarms can be enabled to show in the display and ...

Страница 137: ...atus output and Status mode is set to Alarm item Path Maintenance and diagnostics Diagnostic events Enable alarms Input output events 1 4 2 8 Assign alarm class 4 2 8 1 14 Path 1 No signal Description Warning alarms for Path 1 Setting Process value warning Maintenance demanded Maintenance required Default Maintenance required Path Maintenance and diagnostics Diagnostic events Assign alarm class 14...

Страница 138: ...ut of specification Path Maintenance and diagnostics Diagnostic events Assign alarm class 149 Transm temp below alarm limit 4 3 Maintenance 4 3 1 Copy configuration Description Copy configuration copy configurations from the SensorFlash to the device Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Copy configuration 4 3 2 Spare part replacement 4 3 2 1 Transmitter 4 3...

Страница 139: ...er up Description Operating time total Indicates the total operating time of the transmitter since the last power up 4 3 3 Electronic part identification 4 3 3 1 Transmitter cassette 4 3 3 1 1 HW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Transmitte...

Страница 140: ...cs Maintenance Electronic part identification Transmitter cassette Serial number 4 3 3 1 4 Comm HW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Transmitter cassette Comm HW version 4 3 3 1 5 Comm serial number expert Description Only Siemens authorize...

Страница 141: ...t identification Local dis play HW version 4 3 3 2 2 FW version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification Local dis play FW version 4 3 3 2 3 HMI config version expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK ...

Страница 142: ...tification I O cassette FW version 4 3 3 3 2 Serial number expert Description Only Siemens authorized personnel may replace spare parts Setting Cancel OK Default Cancel Path Maintenance and diagnostics Maintenance Electronic part identification I O cassette Serial number 4 3 3 4 Sensor cassette 4 3 3 4 1 FW version expert Description Only Siemens authorized personnel may replace spare parts Settin...

Страница 143: ...onic part identification Sensor cassette Serial number 4 4 Diagnostics 4 4 1 Sensor 4 4 1 1 Receiver signal Description Receiver signal Path Maintenance and diagnostics Diagnostics Sensor Receiver signal 4 4 1 2 Reynolds number read only Description Calculated Reynolds number Path Maintenance and diagnostics Diagnostics Sensor Reynolds number 4 4 1 3 Path 1 4 4 1 3 1 RxGain up read only Descriptio...

Страница 144: ...nostics Sensor Path 1 SNR up 4 4 1 3 4 SNR down read only Description Signal to noise ration of downstream signal Path Maintenance and diagnostics Diagnostics Sensor Path 1 SNR down 4 4 1 3 5 Sound velocity read only Description Sound velocity Path Maintenance and diagnostics Diagnostics Sensor Path 1 Sound velocity 4 4 1 3 6 Flow velocity read only Description Flow velocity Path Maintenance and d...

Страница 145: ...or Path 1 Travel time down 4 4 1 3 10 Correlation factor read only Description Correlation factor Path Maintenance and diagnostics Diagnostics Sensor Path 1 Correlation factor 4 4 1 3 11 Actual sensor frequency read only Description Sensor frequency Path Maintenance and diagnostics Diagnostics Sensor Path 1 Actual sensor frequency 4 4 1 3 12 Peak amplitude up read only Description Operating time o...

Страница 146: ...lue 4 4 2 2 2 Minimum read only Description Drag indicator of minimum transmitter internal temperature Path Maintenance and diagnostics Diagnostics Temperature monitoring Transmitter elec tronics temperature Minimum 4 4 2 2 3 Timestamp at minimum value read only Description Shows timestamp of recorded minimum transmitter internal temperature Path Maintenance and diagnostics Diagnostics Temperature...

Страница 147: ...Description The set Operation mode can be viewed in this parameter Options Off Current output Default Current output Related In this parameter the setting of Operation mode is read only Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 2 output Operation mode 4 4 3 1 2 Status output signal read only Description The channel value can be viewed in this parameter Related if Oper...

Страница 148: ... mode is set to Pulse output Related This parameter is only available if Operation mode is set to Current output Frequency output or Pulse output Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 2 output Error status 4 4 3 2 Channel 3 relay 4 4 3 2 1 Channel 3 relay Description The channel value can be viewed in this parameter Related This parameter is only available if Oper...

Страница 149: ...ics Diagnostics Inputs and outputs Channel 4 in put output Channel value 4 4 3 3 3 Error status read only Description The error status of the channel can be viewed in this parameter Options Overflow Underflow Fail safe behaviour is activated Operation mode is set to Frequency output Options The pulse output has reached maximum pulse output frequency Fail safe behaviour is activated Operation mode ...

Страница 150: ...s Diagnostics Inputs and outputs Channel 4 in put output Pulse counter 4 4 3 3 5 Reset pulse counter Description The pulse counter can be reset Setting Cancel OK Default Cancel Related This parameter is only available if Operation mode is set to Pulse output Path Maintenance and diagnostics Diagnostics Inputs and outputs Channel 4 in put output Reset pulse counter 4 4 3 4 Calibration picture Descr...

Страница 151: ...tamp at maximum value Minimum value Timestamp at Minimum value and Reset logging will be available Path Maintenance and diagnostics Peak values Process value 1 Process value 4 5 1 2 Maximum Displays maximum measured value Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 1 Maximum value 4 5 1 3 Timestamp at m...

Страница 152: ... values Process value 1 Minimum value timestamp 4 5 1 6 Reset peak values Description This command is used to reset the logging of the recorded maximum and minimum values monitored The drag pointers will be set to the current value Setting Cancel Ok Default Cancel Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process v...

Страница 153: ...tics Peak values Process value 2 Maximum value 4 5 2 3 Timestamp at maximum Displays timestamp when maximum value measured Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 2 Maximum value timestamp 4 5 2 4 Minimum Displays minimum measured value Related This parameter is only available if Process value is no...

Страница 154: ... value 3 4 5 3 1 Process value Description Assign the process value to be monitored Setting Disabled Volume flow Mass flow Sound velocity Flow velocity Density Medium temper ature Kinematic viscosity Totalizer 1 Default Disabled Related If this parameter is set to any other setting than Disabled parameters Maximum value Maximum value timestamp Minimum value Minimum value timestamp and Reset loggin...

Страница 155: ...h Maintenance and diagnostics Peak values Process value 3 Minimum value 4 5 3 5 Timestamp at minimum Displays timestamp when minimum value measured Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 3 Minimum value timestamp 4 5 3 6 Reset peak values Description This command is used to reset the logging of the...

Страница 156: ...ilable Path Maintenance and diagnostics Peak values Process value 4 Assign process value 4 5 4 2 Maximum Displays maximum measured value Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 4 Maximum value 4 5 4 3 Timestamp at maximum Displays timestamp when maximum value measured Related This parameter is only ...

Страница 157: ...set peak values Description This command is used to reset the logging of the recorded maximum and minimum values monitored The drag pointers will be set to the current value Setting Cancel Ok Default Cancel Related This parameter is only available if Process value is not set to Disabled Path Maintenance and diagnostics Peak values Process value 4 Reset logging 4 6 Characteristics 4 6 1 Transmitter...

Страница 158: ...7 2 Installed read only Description Shows the status of the SD card Setting SensorFlash not installed SensorFlash installed SensorFlash used as mass storage de vice Default SensorFlash installed Related Path Maintenance and diagnostics SensorFlash Installed 4 7 3 Capacity total read only Description Total capacity of installed SensorFlash Shows INSERT CARD if card is not installed Setting Default ...

Страница 159: ...tion Description Activation turns on and off data logging activation Setting Off On Default Off Related If this parameter is set to Enabled the parameters Logging value 1 through Logging value 20 can be configured Path Maintenance and diagnostics SensorFlash Data logging Activation 4 7 5 2 Data logging mode Description Select between a momentary value or an averaged value calculated over one loggi...

Страница 160: ...h Data logging Logging interval 4 7 5 4 Process values 4 7 5 4 1 Logging value 1 20 Description The process value to be logged can be selected in this parameter Logged process values are an indicator that you have to stop logging before you can change the logged process values Setting Disabled Volume flow Mass flow Sound velocity Flow velocity Density Medium temper ature Kinematic viscosity Totali...

Страница 161: ...mulation value Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 2 output Operation mode 4 8 1 1 2 Simulation Description Enables or disables simulation of channel 2 current output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics...

Страница 162: ...on Enables or disables simulation of channel 3 relay output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 3 relay Simulation 4 8 1 2 2 Simulation value Description Relay output value to be output when simulati...

Страница 163: ...tput Operation mode 4 8 1 3 2 Simulation Description Enables or disables simulation of Channel 4 input output Setting Disabled Enabled Default Disabled Related Only if this parameter is set to Enabled then the setting of parameter Simulation value will be relevant Path Maintenance and diagnostics Simulation Simulation inputs and outputs Channel 4 input output Simulation 4 8 1 3 3 Simulation value ...

Страница 164: ... 2 Simulation process values 4 8 2 1 Enable simulation Description Select the process value s to be simulated Setting Volume flow Mass flow Flow velocity Sound velocity Density Kinematic viscosity Medi um temperature Default None selected Related Only if process values are marked in this parameter the setting of Simulated value under each relevant process value becomes relevant Path Maintenance an...

Страница 165: ...0 000001 kg h Default 0 0 kg h Related Only if Mass flow is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent on the selected Unit Path Maintenance and diagnostics Simulation Simulation process values Mass flow Simulation value 4 8 2 4 Flow velocity Simulation value Description Set the Flow velocity value to be simulated Set...

Страница 166: ...ected Unit Path Maintenance and diagnostics Simulation Simulation process values Sound velocity Simulation value 4 8 2 6 Density Simulation value Description Set the Density value to be simulated Setting 0 0 kg m3 10000 0 kg m3 Default 1000 0 kg m3 Related Only if Density is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent ...

Страница 167: ...ty Simulation value 4 8 2 8 Medium temperature Simulation value Description Set the Medium temperature value to be simulated Setting 273 0 C 459 399994 F to 400 0 C 752 0 F Default 20 0 C 68 F Related Only if Medium temperature is marked in Enable simulation then the setting of this parameter will be relevant The range and default setting are dependent on the selected Unit Path Maintenance and dia...

Страница 168: ... Various sensor alarms can be selected Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Sensor alarms 1 4 8 3 2 2 Sensor alarms 2 Description The simulation of single and multiple Sensor alarms 2 can be configured Setting Various sensor alarms can be selected Def...

Страница 169: ...larms can be selected Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Process alarms 2 4 8 3 2 5 Process alarms 3 Description The simulation of single and multiple Process alarms 3 can be configured Setting Various process alarms can be selected Default None sel...

Страница 170: ...ning limit Totalizer 1 below alarm limit Default None selected Related This parameter is only available if Simulation mode is set to Simulate alarm ID number Path Maintenance and diagnostics Simulation Simulation alarms Alarms Totalizer alarms 4 8 3 2 8 Input output alarms Description The simulation of single and multiple Input output alarms can be configured Setting Various input output alarms ca...

Страница 171: ...ated can be configured The alarm status is activated on all outputs Setting Failure Function check Out of specification Maintenance required Default None selected Related This parameter can only be accessed if Status icons is set to NAMUR Path Maintenance and diagnostics Simulation Simulation alarms Alarm class 4 9 Audit trail 4 9 1 Parameter change log Displays list of logged parameter changes Lo...

Страница 172: ... 20 logs can be listed with timestamp in the format YYYY MM DD hh mm Path Maintenance and diagnostics Audit trail Firmware update change log 4 9 4 Clear FW update change log expert Description The firmware update log can be reset using this parameter Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Audit trail Clear FW update change log 4 10 Self test 4 10 1 Display test D...

Страница 173: ...ined default values Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Resets Set to default 4 11 2 Device restart write only Description Command to restart device Setting Cancel Ok Default Cancel Related Path Maintenance and diagnostics Resets Device restart 4 12 Firmware update Description The firmware of the device can be updated using a wizard Path Maintenance and diagno...

Страница 174: ...Maintenance and diagnostics 4 12 Firmware update FST020 Function manual 172 Function Manual 09 2017 A5E42949526 AA ...

Страница 175: ...ons Service channel USB USB mode 5 1 2 Auto mode Description The Auto mode can be enabled disabled When auto mode is enabled a device connected via a USB cable is always considered an MSD Setting Disabled Enabled Default Related Path Communications Service channel USB Auto mode 5 1 3 MSD connect write only Description This command is used to connect disconnect to a mass storage device for example ...

Страница 176: ...lt Related Path Communication Modbus Channel 1 Slave address SW 5 2 2 Slave address HW read only Description The slave address HW is determined by the DIP switch setting on the transmitter cassette and can be read out in this parameter This address is used if the DIP switch is set to a value 0 Options Read only Related Path Communication Modbus Channel 1 Slave address HW 5 2 3 Baud rate Descriptio...

Страница 177: ...escription The floating point number byte order used within the data filed of Modbus messages The first mentioned byte is the first byte sent Byte 3 corresponds to the left most byte MSB of a 32 bit floating byte number in big endian format byte 0 to the right most byte Setting 1 0 3 2 0 1 2 3 2 3 0 1 3 2 1 0 Default Related Path Communication Modbus Channel 1 Floating point byte order 5 2 6 Integ...

Страница 178: ...t 0 Requested register 1 Target register 1 Bit 19 Requested register 20 Target register 20 Setting 0 to 1048575 Default Related Path Communication Modbus Channel 1 Register mapping Enable mapping 5 2 7 2 Source register 1 20 Description Modbus register that appears within Modbus request is redirected to the parameter specified by Target register 1 20 Setting Default Related Path Communication Modb...

Страница 179: ...e t min t h t d US Pound lb s lb min lb h lb d Short ton STon min STon h STon d Ton long ton T h T d Custom unit Default kg h Related Path Communications Modbus Channel 1 Modbus units Mass flow unit 5 2 8 2 Volume flow unit Description Set the unit for volume flow values Setting Metric Litre l s l min l h l d Ml d hl s hl min hl h hl d m3 m3 s m3 min m3 h m3 d US Gallons Ugal s Ugal min Ugal h Uga...

Страница 180: ...ic Meter m s m h US Foot ft s ft min Inch in s in min Custom unit Default m s Related Path Communications Modbus Channel 1 Modbus units Flow velocity unit 5 2 8 4 Sound velocity unit Description Set the unit for sound velocity values Setting Metric Meter m s m h US Foot ft s ft min Inch in s in min Custom unit Default m s Related Path Communications Modbus Channel 1 Modbus units Sound velocity uni...

Страница 181: ...ns Modbus Channel 1 Modbus units Density unit 5 2 8 6 Kinematic viscosity unit Description Set the unit for kinematic viscosity values Setting cSt Default cSt Related Path Communications Modbus Channel 1 Modbus units Kinematic viscosity unit 5 2 8 7 Temperature units Description Set the unit for temperature values Setting C F R K Default C Related Path Communications Modbus Channel 1 Modbus units ...

Страница 182: ...ic g kg t US lb STon T oz Custom unit Default kg is set to Mass flow Setting Metric Nl Nm3 Sl Sm3 US Sft3 Default Nl is set to Corrected volume flow Related Path Communications Modbus Channel 1 Modbus units Totalizer 1 unit 5 2 8 9 Service channel USB USB mode read only Description The USB mode can be read in this parameter Options USB communication Mass storage device MSD Related Path Communicati...

Страница 183: ... Change user PIN code 6 2 Change expert PIN code expert Description The Change expert PIN code function can be accessed Setting Default Related Path Security Access management Change expert PIN code 6 3 Recovery ID Displays an ID number required to reset PIN if lost Record this ID number for use when contacting Siemens customer support Setting Default Related Path Security Access management Unique...

Страница 184: ...control function can be configured Setting Disable Enable Default Enable Related Path Security Access management Enable access level control 6 6 Deactivate user PIN Description The Disable access level control function can be configured Setting Disable Enable Default Enable Related Path Security Access management Disable access level control 6 7 Auto logout Description The Auto logout function can...

Страница 185: ... be be configured When the parameter is set to Off default you will not be prompted for password for 10 minutes after the last key press When the parameter is set to On you will be prompted to enter the password before each HMI operation Setting Off On Default Off Related Path Security Access management Auto logout 6 9 Logout Description The Logout function can be configured Setting Default Relate...

Страница 186: ...Security 6 9 Logout FST020 Function manual 184 Function Manual 09 2017 A5E42949526 AA ...

Страница 187: ...FST020 Function manual Function Manual 09 2017 A5E42949526 AA 185 Language 7 7 1 Language Description Select the local display language Setting English Deutsch Default English Related Language Language ...

Страница 188: ...Language 7 1 Language FST020 Function manual 186 Function Manual 09 2017 A5E42949526 AA ...

Страница 189: ... Support on the Internet In addition to our documentation we offer a comprehensive knowledge base online on the Internet at Service and support http www siemens com automation service support There you will find The latest product information FAQs downloads tips and tricks Our newsletter providing you with the latest information about your products Our bulletin board where users and specialists sh...

Страница 190: ...Support A 1 Technical support FST020 Function manual 188 Function Manual 09 2017 A5E42949526 AA ...

Страница 191: ... Hotline 187 I Inputs and outputs 62 Internet Contact person 187 Support 187 L Languages 185 P Paths 29 Pipe settings 19 Process values 38 Q Quick commissioning 17 Quick start wizards 13 S Sensor model 25 Sensor sizes 37 Sensor test blocks 37 Sensor diagnostics 141 Service 187 Service channel USB 173 180 Support 187 T Temperature monitoring 143 Totalizers 57 U User calibration 32 ...

Страница 192: ...Index FST020 Function manual 190 Function Manual 09 2017 A5E42949526 AA ...

Страница 193: ......

Страница 194: ...rives Process Automation 76181 Karlsruhe GERMANY Subject to change without prior notice Order No A5E42949526 Lit No A5E42949526 AA Siemens AG 09 2017 www siemens com processautomation A5E35971532 For more information www siemens com flow ...

Отзывы: