Overview

The floor repeater display is an indication and operation unit in a fire detection system
with the following functions:

Indication of events

Operation

l

Alarm

l

Trouble

l

Supervisory

l

Status

l

Scrolling through lists

l

Reset

l

Acknowledge

l

Unsilence

l

Silence

The display on the floor repeater terminal is synchronized with the fire control panel and
displays the same event texts.

Characteristic

l

Small floor repeater operating, and display panels applied in FC2005/FC901 fire
detection system

l

Large backlight LCD display(160X64)

l

Communication with controller via RS485 (individual addressing)

l

Additional 24 VDC power supply necessary

l

In total, up to 8 FSD can be connected to a fire control panel

l

Access control by key

l

Flat, elegant housing

Содержание FSD901-U2

Страница 1: ...rough lists l Reset l Acknowledge l Unsilence l Silence The display on the floor repeater terminal is synchronized with the fire control panel and displays the same event texts Characteristic l Small floor repeater operating and display panels applied in FC2005 FC901 fire detection system l Large backlight LCD display 160X64 l Communication with controller via RS485 individual addressing l Additio...

Страница 2: ... Trouble Light up in case of trouble event 6 Ground Fault Light up in case of ground fault event 7 Silenced All activated silenceable devices are silenced 8 Supervisory Light up in case of supervisory event 9 Audibles on Light up when NAC or silenceable device is activated 10 Reset Clear all events 11 Acknowledge Acknowledges unacknowledged events 12 Unsilence All silenced devices are activated ag...

Страница 3: ...re reserved for future use Address DIP switch Baud Rate DIP switch 1 2 3 4 7 8 1 On Off Off Off 9600 bps Off Off 2 Off On Off Off 19200 bps On Off 3 On On Off Off 38400 bps Off On 4 Off Off On Off 115200 bps On On 5 On Off On Off 6 Off On On Off 7 On On On Off 8 Off Off Off On FC2005 and FC901 can only support 19200 bps other options reserve for future usage EOL Resistor 2 digit Dip switch S20 is ...

Страница 4: ...mly 5 Connect cables to terminals referring to the connection diagram Fig 3 Correctly set the internal 120Ω EOL resistor referring to the section EOL Resistor 6 Close the front panel FSD connects to separate power supply which needs to be UL Listed for Fire Safety Use and Power Limited Dimension mm Technical data Operating voltage 24 VDC nominal 19 28 VDC Operating current quiescent 60 mA Activati...

Отзывы: