'Network' task card
MP1XS site configuration status
14
343 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
14.10 MP1XS site configuration status
If an MP1XS site configuration (BDV <32) is loaded in Cerberus-Engineering-Tool,
the network configuration is shown as before. The 'Network' > 'Convert to GAP',
'Convert to SAFEDLINK host', 'Convert to ethernet host', and 'Create GAP
configuration' menu items are also available.
It is therefore possible to maintain the
'Site' to status MP1XS and add stations to
it.
However, the 'Site' must be converted in accordance with BDV 32 if the limits of the
site size are exceeded when expanding or merging two 'Sites'.
14.10.1 Converting configuration in accordance with BDV 32
When converting older 'Sites' in accordance with
BDV 32, the new structure is
created for 'Global system configuration' and the references for the
'Stations' are
stored under 'Connections'.
Observe the following points for conversion:
●
Up to 32 'Stations' are permitted in a pure
SAFEDLINK network.
●
The number of 'Stations' in the SAFEDLINK sub-net is limited to 16 in a
heterogeneous network.
The SAFEDLINK sub-net of an older site version could have included up to 32
'Stations'. This number of 'Stations' stations must again be split into several (at
least two) SAFEDLINK sub-nets. Other 'SAFEDLINK sub-net' elements can be
created using the 'New element' function. The 'Fx72x/SAFEDLINK' references
can then be moved to the various sub-nets using the 'Drag and drop', 'Cut' and
'Paste' or 'Unassign' and 'Assign' functions.
●
CAP station no longer exists with its previous function. It is changed into
GAP +
router station.
You will find detailed information on converting in document A6V10260976 and an
overview in document A6V10210416. See chapter 'Applicable documents'.
See also