'Operation' task card
Visibility
13
277 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
'Visible secondary events'
This setting specifies from which normally not visible elements, the activation
messages are displayed if they are activated by an element in the visible part.
You can define the visible event categories in the detail editor of the elements
assigned to the visibility in the 'Overview' tab.
Figure 109: Properties in the detail editor of the element assigned to the visibility
'ALL event categories visible'
If this checkbox is activated, all the event categories are visible.
'Visible event categories'
If only a specific event category is to be visible e.g. 'ALARMS' and 'Faults', you can
define the event category here. The setting is only possible if the 'ALL event
categories visible' checkbox is deactivated.
13.3.2 Standard visibility
The standard visibility defines which events in which elements can be viewed and /
'Station' in
normal operation.
You can configure the visibility as follows:
●
'Site': Visibility for the entire 'Site'
●
'Site without areas': Visibility for all 'Site' events, but not for the detection tree
●
'Station': Visibility of a 'Station' within the 'Site' with all 'Areas' in this 'Station',
incl. 'Hardware tree
●
'Station without areas': Visibility for all 'Station' events, but not for the detection
tree
●
'Area': Visibility for an 'Area' within a 'Station'
Additionally, you can define which event categories are visible for each assigned
element.
While creating a 'Station' the 'Standard visibility' element is pre-configured with
visibility of its own 'Station'. You can add additional elements to the pre-configured